19/160
AB Industrietechnik srl – Via Julius Durst, 70 – 39042 BRESSANONE (BZ) Italy – Tel: +39 0472/830626 – [email protected] – www.industrietechnik.it
4-pipe graph (analogue outputs)
100
0
Temp.
OUT
109
100
0
Temp.
OUT
109
ON
OFF
Temp
Outputs
BS4P
(
I09
)
ON
OFF
Temp
Outputs
BS4P
(
I09
)
(
120
or
121
)
positive
(
120
or
121
)
positive
(
I12
or
I13
)
(
I12
or
I13
)
WCS
WHS
WCS
WHS
WCS
WHS
WCS
WHS
ECONOMY
or
HOLIDAY
ECONOMY
or
HOLIDAY
109: 4-pipe setpoint
WCS: activation point, cooling mode
WHS: activation point, heating mode
Note: the Boost function
(
120
negative) is not available in 4-pipe
mode.
It is possible to display the operating setpoint by configuring the parameter
193
or
194
to 6. In this case, in heating mode, the
value corresponding to
WHS
is displayed, in cooling mode the value corresponding to
WCS
is displayed.
If no contacts are configured in “non-occupied/holiday” or “energy saving / boost” mode, and if the operating mode has
been set manually with timer periods (
Mod
=
tiMb
) and the timer period function
199
=0 (see
“4. Quick access parameter setting”
page 8
), then regulation is controlled within the timer periods with the base setpoints. In this case, “display C”
(see
“3.
Display, keypad and icons” page 7
) shows the active timer period. Outside of the timer period, economy/boost mode is
active.
Otherwise, the contact or sensor status configured in “non-occupied/holiday” or “economy/boost” mode has priority and the
timer periods are not considered (
AH-xxCSx1
models).
If none of the contacts or sensors are configured in “non-occupied/holiday” or “economy/boost” mode and if operating mode
is in holiday mode (manually configured using quick access parameters
→
see
“MODE button functionality” page 10
),
then regulation is controlled with the holiday mode. Otherwise the contact or sensor status configured in the “non-occupied/
holiday” or “economy/boost” mode has priority over the manual configuration.
When timer extension mode is activated manually, it takes priority over energy saving / boost, holiday (see
“28. Timer extension
or forced presence modes” page 109
) and the timer period modes (
AHU-xxCSx1