Register Description
Default
Min
Max
R/W
9139
ANALOG_INPUT3_FUNC
→
Analogue input operation 3 (models AHU-
3xxSx1 excluded)
Analogue input 1 function:
0=not used
1=remote control sensor
2=supply sensor
3=external sensor
4=frost protection heat exchanger sensor
5=0...10 V for air quality sensor (models AHU-3xxSx1 excluded)
6=0....10 V input for humidity sensor (
models AH-3xxSx1 excluded)
7=0...10 V input for pressure transmitter (models AHU-3xxSx1 excluded)
8=season change remote contact (INPUT ON=winter, INPUT OFF=summer)
9=remote On/Off (INPUT ON=OFF, INPUT OFF=ON)
10=non-occupied/holiday (INPUT ON=occupied)
11=economy/boost (INPUT ON=economy activated)
12=forced contact presence (INPUT ON=forced control with base setpoint)
13=frost protection alarm contact (INPUT ON=frost protection active)
14=generic contact alarm (INPUT ON=generic alarm)
15=condensation contact (INPUT ON=condensate alarm)
16=generic filter contact (INPUT ON=generic filter alarm)
17=supply filter contact (INPUT ON=supply filter alarm)
18=extract filter contact (INPUT ON=extract filter alarm)
19=stop all alarm contact (INPUT ON=stop all alarm)
20=fan alarm contact (INPUT ON=fan alarm)
21=frost protection alarm contact for heat exchanger (INPUT ON=frost
protection heat exchanger active)
023
0
0
21
R/W
9140
ANALOG_INPUT3_LOG
→
Analogue input logic 3 (with
023
=8 to 21):
0=normally open (open = INPUT OFF, closed = INPUT ON)
1=normally closed (closed = INPUT OFF, open = INPUT ON)
024
0
0
1
R/W
9141
DIG_OUTPUT1_FUNC
→
Digital output operation 1
0=not used
1=speed 1 for on/off fan
2=speed 2 for on/off fan
3=speed 3 for on/off fan
4=heating valve
5=cooling valve
6=mixed-use valve
7=electrical resistance
8=post-heating valve
9=post-heating electrical resistance
10=authorisation for humidifier
11=external regulated damper
12=external damper
13=bypass damper for cross-flow heat exchanger
14=double battery heat exchanger or on/off rotary heat exchanger
15=pre-heating electrical resistance for heat exchanger
16=on/off humidifier
17=on/off dehumidifier
18=fan alarm output
19=relay for EC motors
20=bypass damper for cross-flow heat exchanger (based on free c/h only)
025
0
0
20
R/W
9142
DIG_OUTPUT2_FUNC
→
Digital output operation 2 (models AHU-0xxSx1
excluded)
0=not used
1=speed 1 for on/off fan
2=speed 2 for on/off fan
3=speed 3 for on/off fan
4=heating valve
5=cooling valve
6=mixed-use valve
7=electrical resistance
8=post-heating valve
9=post-heating electrical resistance
10=authorisation for humidifier
11=external regulated damper
12=external damper
13=bypass damper for cross-flow heat exchanger
14=double battery heat exchanger or on/off rotary heat exchanger
15=pre-heating electrical resistance for heat exchanger
16=on/off humidifier
17=on/off dehumidifier
18=fan alarm output
19=relay for EC motors
20=bypass damper for cross-flow heat exchanger (based on free c/h only)
026
0
0
20
R/W