19. Temperature/humidity control priority
Simultaneous requests for:
- heating and humidification or
- cooling and dehumidification,
are not contradictory and can be controlled together.
However, simultaneous requests for:
- heating and dehumidification
- cooling and humidification
are contradictory and cannot be carried out simultaneously A control priority needs to be assigned between the temperature
and the humidity, using the parameter
212
:
-
212
= 0 means the temperature control is prioritized. The control of the temperature is carried out first; when the temperature
setpoint is reached then humidity control is started.
To do again temperature regulation, temperature must vary as indicated below:
Treg
WCS
Treg
WHS
dT
Heating
(dehumidif)
dT
Cooling
(humidif)
Authorization
0
Authorization
0
Hreg
WDS
Hreg
WUS
dH
Humidification
(cooling)
dH
Dehumidification
(heating)
Authorization
0
Authorization
0
Treg: regulation temperature
WHS: heating operation setpoint
dT: 0.2°C
During dehumidification if Treg < WHS - dT, heating regulation is started and dehumidification regulation stopped till WHS is
reached again
.
Treg
WCS
Treg
WHS
dT
Heating
(dehumidif)
dT
Cooling
(humidif)
Authorization
0
Authorization
0
Hreg
WDS
Hreg
WUS
dH
Humidification
(cooling)
dH
Dehumidification
(heating)
Authorization
0
Authorization
0
Treg: regulation temperature
WCS: cooling operation setpoint
dT: 0.2°C
During humidification if Treg > WCS + dT, cooling regulation is started and humidity regulation stopped till WCS is reached
again.
-
212
= 1 means the humidity control is prioritized. The control of the humidity is carried out first; when the humidity setpoint is
reached then the temperature control is started.
To do again humidity regulation, humidity must vary as indicated below:
Treg
WCS
Treg
WHS
dT
Heating
(dehumidif)
dT
Cooling
(humidif)
Authorization
0
Authorization
0
Hreg
WDS
Hreg
WUS
dH
Humidification
(cooling)
dH
Dehumidification
(heating)
Authorization
0
Authorization
0