If the control temperature drops below WHS, the modulating damper in the presence of free heating conditions goes from
the minimum opening position (parameter
164
) to the maximum opening position (parameter
165
) in the band defined by the
parameter
122
/2.
If Treg < (WHS -
122
) the on/off valve is activated.
If Treg >= (WHS -
122
/2) the on/off valve is disabled.