• Priority humidity,
212
=1:
Humidity setpoint not reached:
Temperature
request
Humidity request
Heating battery
Cooling/
dehumidification
battery
Post-heating
battery
Humidifier
Heating
Humidification
OFF
OFF
OFF
ON
Heating
Dehumidification
OFF
007=0:
ON
(controlled by the
dehumidification
signal)
ON
(controlled by the
supply sensor and the
post-heating setpoint
179)
OFF
007=1:
ON
(dehumidification
using the
modulating or on/off
dehumidifier)
Cooling
Humidification
OFF
OFF
OFF
ON
Cooling
Dehumidification
OFF
007=0:
ON
(controlled with the
max between the
cooling request and
dehumidification
request)
OFF
(if cooling request
is higher than
dehumidification
request)
OFF
ON
(if cooling
request is higher
than dehumidification
request, post heating
is controlled by the
supply sensor and the
post-heating setpoint
179)
007=1:
ON
(dehumidification
using the
modulating or on/off
dehumidifier).