Register Description
Default
Min
Max
R/W
9135
ANALOG_INPUT1_FUNC
→
Analogue input operation 1:
0=not used
1=remote control sensor
2=supply sensor
3=external sensor
4=frost protection heat exchanger sensor
8=season change remote contact (INPUT ON=winter, INPUT OFF=summer)
9=remote On/Off (INPUT ON=OFF, INPUT OFF=ON)
10=non-occupied/holiday (INPUT ON=occupied)
11=economy/boost (INPUT ON=economy activated)
12=forced contact presence (INPUT ON=forced control with base setpoint)
13=frost protection alarm contact (INPUT ON=frost protection
active)
14=generic contact alarm (INPUT ON=generic alarm)
15=condensation contact (INPUT ON=condensate alarm)
16=generic filter contact (INPUT ON=generic filter alarm)
17=supply filter contact (INPUT ON=supply filter alarm)
18=extract filter contact (INPUT ON=extract filter alarm)
19=stop all alarm contact (INPUT ON=stop all alarm)
20=fan alarm contact (INPUT ON=fan alarm)
21=frost protection alarm contact for heat exchanger (INPUT ON=frost
protection heat exchanger active)
019
0
0
21
R/W
9136
ANALOG_INPUT1_LOG
→
Analogue input logic 1 (with
019
=8 to 21):
0=normally open (open = INPUT OFF, closed = INPUT ON)
1=normally closed (closed = INPUT OFF, open = INPUT ON)
020
0
0
1
R/W
9137
ANALOG_INPUT2_FUNC
→
Analogue input operation 2:
0=not used
1=remote control sensor
2=supply sensor
3=external sensor
4=frost protection heat exchanger sensor
8=season change remote contact (INPUT ON=winter, INPUT OFF=summer)
9=remote On/Off (INPUT ON=OFF, INPUT OFF=ON)
10=non-occupied/holiday (INPUT ON=occupied)
11=economy/boost (INPUT ON=economy activated)
12=forced contact presence (INPUT ON=forced control with base setpoint)
13=frost protection alarm contact (INPUT ON=frost protection
active)
14=generic contact alarm (INPUT ON=generic alarm)
15=condensation contact (INPUT ON=condensate alarm)
16=generic filter contact (INPUT ON=generic filter alarm)
17=supply filter contact (INPUT ON=supply filter alarm)
18=extract filter contact (INPUT ON=extract filter alarm)
19=stop all alarm contact (INPUT ON=stop all alarm)
20=fan alarm contact (INPUT ON=fan alarm)
21=frost protection alarm contact for heat exchanger (INPUT ON=frost
protection heat exchanger active)
021
0
0
21
R/W
9138
ANALOG_INPUT2_LOG
→
Analogue input logic 2 (with
021
=8 to 21):
0=normally open (open = INPUT OFF, closed = INPUT ON)
1=normally closed (closed = INPUT OFF, open = INPUT ON)
022
0
0
1
R/W