10. Batteries for temperature and humidity control
The configuration for the AHU batteries for temperature and humidity control is carried out using the following parameters
- heating type battery
002
,
- cooling type battery
003
,
- post-heating type battery
004
.
- humidifier type battery
006
.
- dehumidifier type battery
007
.
Battery
Type of battery
Setting
Heating battery
No heating battery
002
=0
Modulating electrical resistance
002
=1
Modulating heating valve
002
=2
Electrical resistance on/off
002
=3
Heating valve on/off
002
=4
Cooling battery
No cooling battery
003
=0
Modulating cooling valve
003
=1
Cooling valve on/off
003
=2
Mixed-use heating/cooling battery
No mixed-use battery
-
Modulating mixed-use valve
002
=2 and
003
=1
Mixed-use valve on/off
002
=4 and
003
=2
Post-heating battery
No post-heating battery
004
=0
Post-modulating resistance
004
=1
Modulating post-heating valve
004
=2
Post resistance on/off
004
=3
Post-heating valve on/off
004
=4
Humidifier
No humidifier
006
=0
Modulating humidifier
006
=1
Humidifier on/off
006
=2
Dehumidifier
No dehumidifier
007
=0 and
003
=0
Dehumidification through modu-
lating cooling battery
007
=0,
003
=1,
139:1 :or 2:
Modulating dehumidifier
007
=1
Dehumidifier on/off
007
=2
Set the outputs to activate the selected batteries as indicated in the table below:
Element
Settings
Modulating electrical resistance
030
=6 (AO1) or
031
=6 (AO2) or
032
=6 (AO3)
Modulating heating valve
030
=3 (AO1) or
031
=3 (AO2) or
032
=3 (AO3)
Electrical resistance on/off
025
=7 (DO1) or
026
=7 (DO2) or
027
=7 (DO3) or
028
=7 (DO4) or
029
=7 (DO5)
Heating valve on/off
025
=4 (DO1) or
026
=4 (DO2) or
027
=4 (DO3) or
028
=4 (DO4) or
029
=4 (DO5)