Parameter Description
Default
Min
Max
028
Digital output function 4 (models AHU-0xxSx1, AHU-1xxSx1, AHU-2xxSx1, AHU-3xxSx1 excluded)
0=not used
1=speed 1 for on/off fan
2=speed 2 for on/off fan
3=speed 3 for on/off fan
4=heating valve
5=cooling valve
6=mixed-use valve
7=electrical resistance
8=post-heating valve
9=post-heating electrical resistance
10=authorisation for humidifier
11=external regulated damper
12=external damper
13=bypass damper for heat exchanger
14=double battery heat exchanger or on/off rotary heat exchanger
15=pre-heating electrical resistance for heat exchanger
16=on/off humidifier
17=on/off dehumidifier
18=fan alarm output
19=relay for EC motors
20=bypass damper for cross-flow heat exchanger (based on free c/h only)
0
0
20
029
Digital output function 5 (models AHU-0xxSx1, AHU-1xxSx1, AHU-2xxSx1, AHU-3xxSx1 excluded)
0=not used
1=speed 1 for on/off fan
2=speed 2 for on/off fan
3=speed 3 for on/off fan
4=heating valve
5=cooling valve
6=mixed-use valve
7=electrical resistance
8=post-heating valve
9=post-heating electrical resistance
10=authorisation for humidifier
11=external regulated damper
12=external damper
13=bypass damper for heat exchanger
14=double battery heat exchanger or on/off rotary heat exchanger
15=pre-heating electrical resistance for heat exchanger
16=on/off humidifier
17=on/off dehumidifier
18=fan alarm output
19=relay for EC motors
20=bypass damper for cross-flow heat exchanger (based on free c/h only)
0
0
20
030
Analogue output function 1 (models AHU-4xxSx1 excluded):
0=not used
1=supply fan output
2=extractor fan output
3=heating valve output for 2/4-pipe mode
4=cooling valve output for 2/4-pipe mode
5=mixed-use valve output for 2-tube mode
6=modulating electrical resistance output
7=post-heating valve output
8=post-heating electrical resistance output
9=modulating damper output
10=modulating humidifier
11=modulating dehumidifier
12=modulating rotary heat exchanger
13=modulating bypass damper for heat exchanger
0
0
13
031
Analogue output function 2 (models AHU-2xxSx1, AHU-4xxSx1 excluded):
0=not used
1=supply fan output
2=extractor fan output
3=heating valve output for 2/4-pipe mode
4=cooling valve output for 2/4-pipe mode
5=mixed-use valve output for 2-tube mode
6=modulating electrical resistance output
7=post-heating valve output
8=post-heating electrical resistance output
9=modulating damper output
10=modulating humidifier
11=modulating dehumidifier
12=modulating rotary heat exchanger
13=modulating bypass damper for heat exchanger
0
0
13