Parameter Description
Default
Min
Max
009
Type of fan control
0=manual
1=regulation based on CO
2
2=regulation based on temperature
3=regulation based on on/off temperature
4=regulation based on tempCO
2
5=regulation based on pressure (direct action)
6=regulation based on pressure (reverse action)
7=regulation based on dehumidification
0
0
7
010
Type of control damper
0=no damper regulated
1=on/off regulated
2=on/off bypass for heat exchanger
3=external modulating damper
4=modulating bypass for heat exchanger
5=on/off bypass for cross-flow heat exchanger (free H/C only)
0
0
5
011
Damper action
0=CO
2
1=free cooling/heating
2=free cooling/heating, CO
2
3=dehumidification
1
0
3
012
Type of heat exchanger
0=non-controlled heat exchanger
1=cross-flow heat exchanger
2=double battery heat exchanger
3=rotary on/off heat exchanger
4=modulating rotary heat exchanger
0
0
4
013
Activation of mid-season operation
0=not enabled
1=enabled
0
0
1
014
Unit regulation type
0=fixed point control for 2-pipe operation
1=control with offset for 2-pipe operation
2=cascade control
3=fixed point control for 4-pipe operation
4=control with compensation for 4-pipe operation
0
0
4
015
Digital input 1 function:
0=not used
1=remote season change (INPUT ON=winter, INPUT OFF=summer)
2=remote On/Off (INPUT ON=OFF, INPUT OFF=ON)
3=non-occupied holiday (INPUT ON=Occupied)
4=economy/boost (INPUT ON = economy activated)
5=forced presence contact (INPUT ON = forced -> control with base setpoint)
6=frost protection (INPUT ON=frost protection alarm)
7=generic alarm (INPUT ON=generic alarm)
8=condensation contact (INPUT ON=condensation alarm)
9=generic filter contact (INPUT ON=generic filter alarm)
10=supply filter contact (INPUT ON=supply filter alarm)
11=extractor filter contact (INPUT ON=extractor filter alarm)
12=stop all alarm contact (INPUT ON=stop all alarm)
13=fan alarm contact (INPUT ON=fan alarm)
14=frost protection heat exchanger contact (INPUT ON=frost protection heat exchanger alarm)
0
0
14
016
Digital input 1 contact logic:
0=normally open (open = INPUT OFF, closed = INPUT ON)
1=normally closed (closed = INPUT OFF, open = INPUT ON)
0
0
1
017
Digital input 2 function:
0=not used
1=remote season change (INPUT ON=winter, INPUT OFF=summer)
2=remote On/Off (INPUT ON=OFF, INPUT OFF=ON)
3=non-occupied holiday (INPUT ON=Occupied)
4=economy/boost (INPUT ON = economy activated)
5=forced presence contact (INPUT ON = forced -> control with base setpoint)
6=frost protection (INPUT ON=frost protection alarm)
7=generic alarm (INPUT ON=generic alarm)
8=condensation contact (INPUT ON=condensation alarm)
9=generic filter contact (INPUT ON=generic filter alarm)
10=supply filter contact (INPUT ON=supply filter alarm)
11=extractor filter contact (INPUT ON=extractor filter alarm)
12=stop all alarm contact (INPUT ON=stop all alarm)
13=fan alarm contact (INPUT ON=fan alarm)
14=frost protection heat exchanger contact (INPUT ON=frost protection heat exchanger alarm)
0
0
14