• Analogue inputs
1. Analogue input 1 (
AI1
):
Parameter
Logic
019
=0
Sensor not used
019
=1
Remote regulation
sensor
The
AI1
sensor is used together with the internal sensor to obtain the final room regulation
temperature according to the parameter
106
(see
“8. Control sensors” page 16
:
019
=2
Supply sensor
The
AI1
sensor is used as a limit sensor for fixed-point regulation with limits (
125
and/or
127
not equal to 0), or as a regulation sensor for the valves (
001
=1), or as a regulation sensor in
the cascade regulation (
014
=2).
019
=3
External sensor
The
AI1
sensor is used for the compensation (
130
not equal to 0)
019
=4
Frost protection
heat exchanger
sensor
The
AI1
sensor is used as a frost protection
heat exchanger
sensor
019
=5 to 7
Not selectable by the
AI1
sensor
019
=8
Remote season
change contact
020
=
0
1
Summer
Winter
019
=9
Remote on/off
contact
020
=
0
1
On
Off
019
=10
Non-occupied/
holiday remote
contact
020
=
0
1
“Non-occupied holiday” mode
“Occupied” mode
019
=11
Energy savings
remote contact
020
=
0
1
No economy/boost mode
Economy/boost mode
019
=12
Forced presence
contact
020
=
0
1
No forced presence
Forced presence
019
=13
Heat frost protection
battery contact
020
=
0
1
Frost protection off
Frost protection on
019
=14
Generic
alarm contact
020
=
0
1
No alarm
Alarm active
019
=15
Condensation
alarm contact
020
=
0
1
No condensation
Condensation alarm
019
=16
Generic filter
alarm contact
020
=
0
1
No generic filter alarm
Generic filter alarm
019
=17
Supply filter
alarm contact
020
=
0
1
No supply filter alarm
Supply filter alarm