Register Description
Default
Min
Max
R/W
9246
DAYLIGHT_SAVING_TIME
→
Change to/from daylight savings time
0=no automatic update of summertime change
1=automatic summertime change in Europe
2=automatic summertime change in the USA
197
1
0
2
R/W
9247
TIME_TIMER_PROLUNG
→
Duration of extension timer (minutes)
198
60
1
480
R/W
9248
TIME_BAND_FUNCTION
→
Timer periods operation
0=timer periods for normal/economy-boost operation
1=timer periods to switch on/off the appliance
199
0
0
1
R/W
9249
MODBUS_BAUD
→
Baud rate of the Modbus (1=2400, 2=4800, 3=9600,
4=19200, 5=38400 bit/s)
(for
AHU-xMxSx1
models only)
200
4
1
5
R/W
9250
MODBUS_PARITY
→
Parity of the modbus (0=none, 1=odd, 2=even)
(for
AHU-xMxSx1
models only)
201
2
0
2
R/W
9251
MODBUS_ADDRESS
→
Appliance address on the Modbus network
(1…247)
(for
AHU-xMxSx1
models only)
202
1
1
247
R/W
9252
CANCEL_HOURS_FAN_RUN
→
Reset hours counter for hours of operation
of the fan
203
0
0
1
R/W
9253
COMFORT_FUNCTION
→
COMFORT function
0=current setpoint, modified via quick access
1=setpoint offset, modified via quick access
204
0
0
1
R/W
9254
OFFSET_RANGE
→
Setpoint offset range applied in the comfort function
(Δ°C [Δ°F])
(Note1)
205
30 [5]
0[0]
100 [18]
R/W
9255
RANGE_MIN_VOLT_INPUT
→
Low scale for input 0...10 V
206
0
-50
207
R/W
9256
RANGE_MAX_VOLT_INPUT
→
High scale for input 0...10 V
207
2000
206
9999
R/W
9257
UNIT_VOLT_INPUT
→
Unit of measurement of display B for input 0...10 V
0=ppm
1=% R.H.
2=no unit
208
0
0
2
R/W
9258
COR_AI3_VOLT_INPUT
→
Correction of input 0...10 V
AI3
209
0
-980
980
R/W
9259
PRIORITY_MANUAL_OFF
→
Manual switch-off priority
0=manual on/off has not priority
1=manual on/off has priority
210
0
0
1
R/W
9260
LIMIT_MANUAL_SPEED
→
Manual speed limit
211
50
15
100
R/W
9261
PRIORITY_TEMP_HUM
→
Temperature/humidity control priority
0=temperatura priority
1=humidity priority
212
0
0
1
R/W
9262
OFFSET_SETPOINT
→
Setpoint offset in the comfort function (Δ°C [Δ°F])
(Note1)
0 [0]
-
205
205
R/W
9263
MODE_FASCE
→
Selecting the operating mode
0=without time periods
1=with time periods
2=holidays
0
0
2
R/W
9264
MANUAL_OCCUPANCY
→
Forced control as if in a timer period interval
0=no forced control
1=for a duration corresponding to the parameter
198
0
0
1
R/W
9265
STA_MANUAL
→
Selecting the 2-pipe operating season
0=winter
1=summer
0
0
1
R/W
9266
FAN_SPEED_MODE
→
Selecting the fan speed manually
0=manual speed 1
1=manual speed 2
2=manual speed 3
0
0
2
R/W
9267
ON_OFF_VIA_MODBUS
→
On/off via Modbus
0= OFF, 1= ON
1
0
1
R/W
9268
YEAR_SET
→
Year to set
2012
2012
2100
R/W
9269
MONTH_SET
→
Month to set
1
1
12
R/W
9270
DAY_SET
→
Day to set
1
1
31
R/W
9271
HOUR_SET
→
Hour to set
0
0
23
R/W
9272
MIN_SET
→
Minute to set
0
0
59
R/W
9273
ABI_CLOCK_SET_FROM_MODBUS
→
To update the clock via Modbus, first
set the year, month, day, hour, minutes in the registers 9268 to 9272. Then set
the register 9273 to 1. The settings made are then automatically loaded into the
appliance clock and register 9273 resets to 0.
0
0
1
R/W
9274
RESET_PARAM_TO_DEFAULT
→
set the parameter to 1 to reload the default
values. The parameter resets to 0 once the procedure has terminated successfully
0
0
1
R/W