• Heating operation using free heating:
Operation with modulating damper and modulating heating valve:
Do following settings:
-
170
=2 or 3 (authorization of free heating regardless the working season), or
170
=5 or 6 (authorization of free heating in heat
-
ing mode only),
- do the regulation on room sensor (internal or remote sensor)
001
=0;
in case the remote sensor is used set an analogue input as remote sensor
019
=1 (AI1) or
021
=1 (AI2) or
023
=1 (AI3)),
- set an analogue input as external sensor
019
=3 (AI1) or
021
=3 (AI2) or
023
=3 (AI3),
- external modulating damper regulated on free c/h:
010
=3,
011
=1 or 2 and
030
=9 (AO1) or
031
=9 (AO2) or
032
=9 (AO3),
or modulating bypass for heat exchanger
010
=4,
011
=1 and
012
=1,
030
=13 (AO1) or
031
=13 (AO2) or
032
=13 (AO3).
- modulating heating valve
002
=2 and
030
=3 (AO1) or
031
=3 (AO2) or
032
=3 (AO3)
or modulating mixed-use valve in heating
002
=2
003
=1 and
030
=5 (AO1) or
031
=5 (AO2) or
032
=5 (AO3)
or modulating electrical resistance
002
=1 and
030
=6 (AO1) or
031
=6 (AO2) or
032
=6 (AO3)
100%
0%
Treg
114
WHS
114
/2
100%
0%
Treg
116
WCS
116
/2
100%
0%
Treg
114
WHS
114
/2
100%
0%
Treg
116
WCS
116
/2
100%
0%
Treg
122
WHS
122
/2
100%
0%
Treg
122
WCS
122
/2
100%
0%
Treg
122
WHS
122
/2
100%
0%
Treg
122
WCS
122
/2
100%
0%
Treg
WHS
123
178
100%
0%
Treg
WHS
123
178
100%
0%
Treg
WCS
123
178
100%
0%
Treg
WCS
123
178
Treg: control temperature
WHS: heating operation setpoint
114
:
heating proportional band
solid curve: modulating damper output
dashed curve: modulating heating valve output
If the control temperature drops below WHS, the modulating damper in the presence of free heating conditions goes from
the minimum opening position (parameter
164
) to the maximum opening position (parameter
165
) in the band defined by the
parameter
114
/2.
The valve changes position from closed to open when Treg change from (WHS -
114
/2) to (WHS -
114
).
Operation with modulating bypass damper without heating valve
Do following settings:
-
170
=2 or 3 (authorization of free heating regardless the working season), or
170
=5 or 6 (authorization of free heating in heat
-
ing mode only),
- do the regulation on room sensor (internal or remote sensor)
001
=0;
in case the remote sensor is used set an analogue input as remote sensor
019
=1 (AI1) or
021
=1 (AI2) or
023
=1 (AI3)),
- set an analogue input as external sensor
019
=3 (AI1) or
021
=3 (AI2) or
023
=3 (AI3),
- serranda modulante bypass per recuperatore
010
=4,
011
=1 and
012
=1 and
030
=13 (AO1) or
031
=13 (AO2) or
032
=13 (AO3).
100%
0%
Treg
114
WHS
114
/2
100%
0%
Treg
116
WCS
116
/2
100%
0%
Treg
114
WHS
114
/2
100%
0%
Treg
116
WCS
116
/2
100%
0%
Treg
122
WHS
122
/2
100%
0%
Treg
122
WCS
122
/2
100%
0%
Treg
122
WHS
122
/2
100%
0%
Treg
122
WCS
122
/2
100%
0%
Treg
WHS
123
178
100%
0%
Treg
WHS
123
178
100%
0%
Treg
WCS
123
178
100%
0%
Treg
WCS
123
178
100%
0%
Treg
178
WHS
100%
0%
Treg
178
WCS
Treg: control temperature
WHS: heating operation setpoint
178
hysteresis regulation free heating/cooling
If the control temperature drops below WHS, the modulating bypass damper in the presence of free heating conditions goes
from the minimum opening position (parameter
164
) to the maximum opening position (parameter
165
) in the band defined by
the parameter
178
.