Humidity setpoint reached, temperature control:
Temperature
request
Humidity request
Heating battery
Cooling/
dehumidification
battery
Post-heating
battery
Humidifier
Heating
Humidification
achieved
ON
OFF
005=0
(post only)
:
OFF
OFF
005=1
(post+integ)
ON
(controlled in
integration through
the control sensor
and the WHS
operating setpoint)
Heating
Dehumidification
achieved
ON
OFF
005=0
(post only)
:
OFF
OFF
005=1
(post+integ)
ON
(controlled in
integration through
the control sensor
and the WHS
operating setpoint)
Cooling
Humidification
achieved
OFF
007=0:
ON
(temperature-
controlled)
OFF
OFF
007=1 or 2:
OFF
(dehumidification
using the
modulating or on/off
dehumidifier)
Cooling
Dehumidification
achieved
OFF
ON
(controlled by
temperature).
OFF
OFF
007=1 or 2:
OFF
(dehumidification
using the
modulating or on/off
dehumidifier)