10/160
AB Industrietechnik srl – Via Julius Durst, 70 – 39042 BRESSANONE (BZ) Italy – Tel: +39 0472/830626 – [email protected] – www.industrietechnik.it
• MODE button functionality
Depending on the value of parameter
195
, the function is selected by quick access by pressing the MODE button. The
other 2 functions can, however, be accessed by pressing the
ESC
M
O
D
E
buttons.
Access to the rapid function using the MODE button:
• If
195
=0 (quick access to the local season change configuration if no contact is configured as remote season change)
Press the
M
O
D
E
button, the
“HEAT”
(for heating) or
“COOL”
(for cooling) icon flashes depending on the current configuration
and the same flashing text appears on
display B.
Press the
M
O
D
E
button to change the setting. The value is automatically saved. To exit the menu, wait for 4 seconds or press
the
ESC
button.
• If
195
=1 (quick access to the timer extension configuration)
The extended running function extends operation with the base setpoint by excluding the economy function and the
“non-occupied holiday” function for a time corresponding to parameter
198
if the timer function parameter
199
=0.
With
199
=1 (switch on/off using the timer) the timer extension function enables continued operation in the ON mode
by excluding the timer periods for a period of time corresponding to parameter
198
.
Press the
M
O
D
E
button,
noOC
flashes on the
display B
(to stop the timer extension if started) or
OC
and the icon flashes on
display B
(to activate the timer extension).
Press the
M
O
D
E
button to change the setting. The value is automatically saved.
To exit the menu, wait for 4 seconds or press the
ESC
button.
• If
195
=2 (quick access to the operating mode configuration)
The operating mode function is used to select whether to control with or without the timer periods
(if the parameter
199
=0,
it is controlled using the timer periods
see
“6. TIMER PERIODS operation and configuration (Model AHU-xxCSx1)”
page 12
) or with “non-occupied/holiday” mode (see
“9. Operating setpoint, economy/BOOST, holiday modes”
page 17
).
If
199
=0 the timer periods are functioning for normal/economy-boost operation:
push the
M
O
D
E
button,
nOrM
flashes on
display B
(for control without the timer periods) or
tiMB
flashes on
display B
and the icon (for normal/economy-boost control using the timer periods) or
HOLY
flashes on
display B
and the icon (for control in the “non-occupied/holiday” mode).
If
199
=1 the timer periods are functioning for switching the unit on/off:
push the
M
O
D
E
button,
nOrM
flashes on
display B
(for control without the timer periods) or
HOLY
flashes on
display B
and the icon (for control in “non-occupied/holiday” mode).
Press the
M
O
D
E
button one or more times to select the control mode. The value is automatically saved.
To exit the menu, wait for 4 seconds or press the