• Free heating in the summer:
Operation with modulating damper:
Do following settings:
-
170
=2 or 3 (authorization of free heating regardless the season),
- do the regulation on room sensor (internal or remote sensor)
001
=0;
in case the remote sensor is used set an analogue input as remote sensor
019
=1 (AI1) or
021
=1 (AI2) or
023
=1 (AI3)),
- set an analogue input as external sensor
019
=3 (AI1) or
021
=3 (AI2) or
023
=3 (AI3),
- external modulating damper regulated on free c/h:
010
=3,
011
=1 or 2 and
030
=9 (AO1) or
031
=9 (AO2) or
032
=9 (AO3),
or modulating bypass for heat exchanger
010
=4,
011
=1 and
012
=1,
030
=13 (AO1) or
031
=13 (AO2) or
032
=13 (AO3).
100%
0%
Treg
114
WHS
114
/2
100%
0%
Treg
116
WCS
116
/2
100%
0%
Treg
114
WHS
114
/2
100%
0%
Treg
116
WCS
116
/2
100%
0%
Treg
122
WHS
122
/2
100%
0%
Treg
122
WCS
122
/2
100%
0%
Treg
122
WHS
122
/2
100%
0%
Treg
122
WCS
122
/2
100%
0%
Treg
WHS
123
178
100%
0%
Treg
WHS
123
178
100%
0%
Treg
WCS
123
178
100%
0%
Treg
WCS
123
178
Treg: control temperature
WCS: cooling operation setpoint
123
: neutral zone
178
: hysteresis for control of free heating/cooling
If the control temperature drops below WCS -
123,
the modulating damper in the presence of free heating goes from the
minimum opening position (parameter
164
) to the maximum opening position (parameter 1
65
) in the band defined by the
parameter
178
.
Note: if external modulating damper is used, the presence of the cooling battery is mandatory:
on/off cooling valve
003
=2 and
025
=5 (DO1) or
026
=5 (DO2) or
027
=5 (DO3) or
028
=5 (DO4) or
029
=5 (DO5),
or on/off mixed-use valve in cooling
002
=4,
003
=2 and
025
=6 (DO1) or
026
=6 (DO2) or
027
=6 (DO3) or
028
=6 (DO4) or
029
=6
(DO5),
or modulating cooling valve
003
=1 and
030
=4 (AO1) or
031
=4 (AO2) or
032
=4 (AO3),
or modulating mixed-use cooling valve
002
=2
003
=1 and
030
=5 (AO1) or
031
=5 (AO2) or
032
=5 (AO3).
if modulating bypass damper is used, the presence of the cooling battery is not mandatory
Operation with on/off damper:
Do following settings:
-
170
=2 or 3 (authorization of free heating regardless the season),
- do the regulation on room sensor (internal or remote sensor)
001
=0;
in case the remote sensor is used set an analogue input as remote sensor
019
=1 (AI1) or
021
=1 (AI2) or
023
=1 (AI3)),
- set an analogue input as external sensor
019
=3 (AI1) or
021
=3 (AI2) or
023
=3 (AI3),
- external on/off damper controlled by free cooling/heating:
010
=1 and
025
=11 (DO1) or
026
=11 (DO2) or
027
=11 (DO3) or
028
=11 (DO4) or
029
=11 (DO5),
100%
0%
Treg
114
WHS
114
/2
100%
0%
Treg
116
WCS
116
/2
100%
0%
Treg
114
WHS
114
/2
100%
0%
Treg
116
WCS
116
/2
100%
0%
Treg
122
WHS
122
/2
100%
0%
Treg
122
WCS
122
/2
100%
0%
Treg
122
WHS
122
/2
100%
0%
Treg
122
WCS
122
/2
100%
0%
Treg
WHS
123
178
100%
0%
Treg
WHS
123
178
100%
0%
Treg
WCS
123
178
100%
0%
Treg
WCS
123
178
Treg: control temperature
WCS: cooling operation setpoint
123
: neutral zone
178
: hysteresis for control of free heating/cooling
In the presence of free heating conditions:
If Treg < (WCS -
123
-
178
) the on/off damper is activated.
If Treg >= (WHS -
123
) the damper is disabled.
Note: the presence of the cooling battery is mandatory: