Register Description
Default
Min
Max
R/W
9191
SETPOINT_HUMIDITY
→
Humidity setpoint
(Note2)
142
500
0
1000
R/W
9192
PROP_BAND_HUMIDITY
→
Proportional band for humidity
(Note2)
143
50
20
1000
R/W
9193
INTEGRAL_TIME_HUMIDITY
→
Integral time for humidity (s)
144
0
0
999
R/W
9194
AUTHORIZE_LOW_LIM_SUPPLY_HUM
→
Activation of low limit supply for
humidity
0=not enabled
1=enabled
145
0
0
1
R/W
9195
SET_LIM_LOW_HUM
→
Low limit supply humidity setpoint (%r.h.)
(Note2)
146
200
100
500
R/W
9196
AUTHORIZE_HIGH_LIM_SUPPLY_HUM
→
Activation of high limit supply
for humidity
0=not enabled
1=enabled
147
0
0
1
R/W
9197
SET_LIM_HIGH_HUM
→
High limit supply humidity setpoint (%r.h.)
(Note2)
148
750
500
900
R/W
9198
PROP_BAND_LIM_HUM
→
Proportional band for the humidity limit (%r.h.)
(Note2)
149
50
30
300
R/W
9199
MIN_VOLT_SUPPLY_FAN
→
Minimum supply fan voltage
(Note3)
150
0
0
151
R/W
9200
MAX_VOLT_SUPPLY_FAN
→
Maximum supply fan voltage
(Note3)
151
100
150
100
R/W
9201
MIN_VOLT_EXTRACT_FAN
→
Minimum extractor fan voltage
(Note3)
152
0
0
153
R/W
9202
MAX_VOLT_EXTRACT_FAN
→
Maximum extractor fan voltage
(Note3)
153
100
152
100
R/W
9203
SPEED_1_MODULATING
→
Speed 1 of the modulating fans (%)
154
10
0
100
R/W
9204
SPEED_2_MODULATING
→
Speed 2 of the modulating fans (%)
155
65
0
100
R/W
9205
SPEED_3_MODULATING
→
Speed 3 of the modulating fans (%)
156
100
0
100
R/W
9206
ISTERESIS_FAN
→
Fan hysteresis (with fan control in temperature)
(Δ°C [Δ°F])
(Note1)
157
10 [18]
10 [18]
50 [90]
R/W
9207
STEP_START_MOD_FAN
→
Step activation of modulating fans (%)
158
10
0
100
R/W
9208
DELAY_START_REG
→
Startup regulation delay (s)
159
0
0
600
R/W
9209
DELAY_STOP_FAN
→
Stop delay of ventilation (s)
160
30
0
600
R/W
9210
SETPOINT_PRESSURE
→
Pressure setpoint
161
1500
206
207
R/W
9211
PROP_BAND_PRESSURE
→
Proportional band for humidity
162
300
1
1000
R/W
9212
INTEGRAL_TIME_PRESSURE
→
Integral time for pressure (s)
163
0
0
999
R/W
9213
MIN_OPENING_POS_DAMPER
→
Minimum modulating damper
opening (%)
164
10
0
165
R/W
9214
MAX_OPENING_POS_DAMPER
→
Maximum modulating damper
opening (%)
165
100
164
100
R/W
9215
DAMPER_STOP_DELAY
→
Stop delay of damper (s)
166
30
0
600
R/W
9216
SETPOINT_AIR
→
Air exchange setpoint
167
1000
0
2000
R/W
9217
PROP_BAND_AIR
→
Air exchange proportional band
168
200
50
2000
R/W
9218
INTEGRAL_TIME_AIR
→
Integral time for air exchange
169
0
0
999
R/W
9219
AUTHORIZE_FREE_COOL_HEAT
→
Activation of free cooling/heating
0=not enabled
1=free cooling enabled
2=free heating enabled
3=free cooling and heating enabled
4=free cooling in cooling only enabled
5=free heating in heating only enabled
6=free cooling in cooling only and free heating in heating only enabled
170
0
0
6
R/W
9220
SETPOINT_DIFF_FREE_HEAT_COOL
(°C [°F])
(Note1)
→
Differential setpoint
for free cooling/heating
171
40 [72]
4 [8]
100 [180]
R/W
9221
DIFF_FREE_COOL_HEAT
→
Free cooling/heating proportional band
(°C [°F])
(Note1)
172
20 [36]
4 [8]
100 [180]
R/W
9222
SETPOINT_DIFF_FREE_COOL_HEAT_MAX
→
Maximum differential
setpoint for free cooling/heating
(°C [°F])
(Note1)
173
100 [180]
50 [90]
200 [360]
R/W
9223
TEXT_MIN_FREE_COOL
→
Minimum external temperature for free cooling
(°C [°F])
(Note1)
174
170 [63]
100 [50]
200 [68]
R/W
9224
TREG_MIN_FREE_COOL
→
Minimum control temperature for free cooling
(°C [°F])
(Note1)
175
220 [72]
150 [59]
300 [86]
R/W
9225
TEXT_MAX_FREE_HEAT
→
Maximum external temperature for free
heating
(°C [°F])
(Note1)
176
280 [82]
200 [68]
350 [95]
R/W
9226
TREG_MAX_FREE_HEAT
→
Maximum control temperature for free heating
(°C [°F])
(Note1)
177
330 [91]
200 [68]
350 [95]
R/W
9227
HYST_REG_FREE_HEAT
→
Hysteresis for free heating/cooling
(°C [°F])
(Note1)
178
10 [18]
5 [10]
100 [180]
R/W
9228
SET_POST_HEATING
→
Post-heating setpoint (Δ°C [Δ°F])
(Note1)
179
240[75]
50 [41]
500 [122]
R/W