38. Resetting the default parameters
The initial (default) configuration of the parameters can be reloaded as follows:
Press the
and
buttons together to access the main menu. The following screen is displayed:
CLK
yMdH
(model
AHU-xxCSx1
) or
AL
noAL
(model
AHU-xxSSx1
)
Press the
or
button until the following screen is displayed:
PAS
1
Press the button and then the
button until the value
33
is displayed.
Press the button to access the default parameters reset level.
R01
0
To cancel and return to the controller, press the
ESC
button.
To activate the procedure, press the button, the value 0 starts to flash. Press the
button to change the value to 1 and
press the
button again.
The reset procedure starts, the display reports the following messages:
Li
loading default settings begins
Ld
default parameters loaded.
When the following screen appears again, it is possible to exit the menu by pressing the
ESC
button once, or by waiting for
around 120 seconds.
R01
0