Register Description
Min
Max
R/W
10033
CURRENT_WORKING_HUM_SET
→
current humidity operation setpoint
(Note5)
see controllers.
see controllers.
R
10034
CURRENT_WORKING_POST_SET
→
current post-heating operation setpoint
(Note2)
see controllers.
see controllers.
R
10035
FLAG_GLOBAL_ON/OFF
0=switched off using remote contact
1=switched off using timer
2=switched off using keyboard
3=switched off using Modbus
4=switched on using remote contact
5=switched on using timer
6=switched on using keyboard
7=switched on using Modbus
0
7
R
10036
FLAG_CURRENT_MODE_REG
→
control status
0=control without the timer periods
1=normal control (within a timer period interval if
199
=0)
2=normal control forced manually (“Oc” for the duration of the
198
timer)
3=economy control
4=non-occupied/holiday mode control
0
4
R
10037
FLAG_STA_WORKING
→
operating season status
0=heating
1=cooling
0
1
R
10038
FLAG_HEATING
→
heating status
0=heating in progress
1=heating stopped
0
1
R
10039
FLAG_ELECTRIC_HEATER
→
electrical resistance status
0=electrical resistance ON
1=electrical resistance OFF
0
1
R
10040
FLAG_COOLING
→
cooling status
0=cooling in progress
1=cooling stopped
0
1
R
10041
FLAG_POST_HEATING
→
post-heating status
0=post-heating in progress
1=post-heating stopped
0
1
R
10042
FLAG_FROST_PROTECTION
→
frost protection heating battery status
0=frost protection alarm not present
1=frost protection alarm
0
1
R
10043
FLAG_FREE_COOLING_CONDITION
→
free cooling condition
0=conditions for free cooling present
1= conditions for free cooling not present
0
1
R
10044
FLAG_FREE_HEATING_CONDITION
→
free heating condition
0=conditions for free heating present
1= conditions for free heating not present
0
1
R
10045
FLAG_CURRENT_SPEED
→
one or more speed fan status ON/OFF
0=fan coil off
1=fan coil at speed 1 for ON/OFF 3-speed fan coil
2=fan coil at speed 2 for ON/OFF 3-speed fan coil
3=fan coil at speed 3 for ON/OFF 3-speed fan coil
0
3
R
10046
FLAG_CURRENT_SPEED_SUPPLY_EXTRACT
→
modulating supply fan status (or
extract fan status if supply fan not present)
0=fan coil off
1=fan converter at speed 1
2=fan converter at speed 2
3=fan converter at speed 3
0
3
R
10047
FLAG_LIM_ALARM
→
temperature limit alarm status
0=no limit alarm
1=low limit alarm
2=high limit alarm
0
2
R
10048
FLAG_DEHUMIDIFICATION
→
dehumidification status
0=dehumidification in progress
1=dehumidification stopped
0
1
R
10049
FLAG_HUMIDIFICATION
→
humidification status
0=humidification in progress
1=humidification stopped
0
1
R
10050
FLAG_DIRTY_FILTER
→
fan filter status
0=fan filter clean
1=fan filter dirty (has exceeded the operational hours defined by parameter
192
.
0
1
R
10051
FLAG_DECREASE_CO2
→
status of
CO
2
decrease
0=air exchange finished
1=air exchange in progress
0
1
R
10052
FLAG_EXCHANGER_FROST_PROTECTION
→
frost protection heat exchanger status
0=frost protection alarm not present in the heat exchanger
1=frost protection alarm present in the heat exchanger
0
1
R