144/160
AB Industrietechnik srl – Via Julius Durst, 70 – 39042 BRESSANONE (BZ) Italy – Tel: +39 0472/830626 – [email protected] – www.industrietechnik.it
Register Description
Default
Min
Max
R/W
9126
TYPE_DAMPER
→
Type of controlled damper
0=no control damper
1=on/off control
2=on/off bypass for heat exchanger
3=external modulating damper
4=modulating bypass for heat exchanger
5=on/off bypass for cross-flow heat exchanger (free H/C only)
010
0
0
5
R/W
9127
REG_TYPE_DAMPER
→
Damper action
0=
CO
2
1=free cooling/heating
2=free cooling/heating,
CO
2
3=dehumidification
011
1
0
3
R/W
9128
TYPE_HEAT_EXCHANGER
→
Type of heat exchanger
0=non-controlled heat exchanger
1=cross-flow heat exchanger
2=double battery heat exchanger
3=rotary on/off heat exchanger
4=modulating rotary heat exchanger
012
0
0
4
R/W
9129
ACTIV_HALF_SEASON_MODE
→
Activation of mid-season operation
0=not enabled
1=enabled
013
0
0
1
R/W
9130
CONTROL_STATE
→
Type of appliance control
0=fixed point control for 2-pipe operation
1=control with offset for 2-pipe operation
2=cascade control
3=fixed point control for 4-pipe operation
4=control with compensation for 4-pipe operation
014
0
0
4
R/W
9131
DIG_INPUT1_FUNC
→
Digital input operation 1:
0=not used
1=remote season change (INPUT ON=winter, INPUT OFF=summer)
2=remote On/Off (INPUT ON=OFF, INPUT OFF=ON)
3=non-occupied holiday (INPUT ON=Occupied)
4=economy/boost (INPUT ON = economy activated)
5=forced contact presence (INPUT ON=forced control with base setpoint)
6=frost protection alarm contact (INPUT ON=frost protection active)
7=generic alarm contact (INPUT ON=generic alarm)
8=condensation contact (INPUT ON=condensate alarm)
9=generic filter contact (INPUT ON=generic filter alarm)
10=supply filter contact (INPUT ON=supply filter alarm)
11=extraction filter contact (INPUT ON=extractor filter alarm)
12=stop all alarm contact (INPUT ON=stop all alarm)
13=fan alarm contact (INPUT ON=fan alarm)
14=frost protection alarm contact of heat exchanger (INPUT ON=frost
protection heat exchanger active)
015
0
0
14
R/W
9132
DIG_INPUT1_LOG
→
Digital input contact logic 1:
0=normally open (open = INPUT OFF, closed = INPUT ON)
1=normally closed (closed = INPUT OFF, open = INPUT ON)
016
0
0
1
R/W
9133
DIG_INPUT2_FUNC
→
Digital input operation 2:
0=not used
1=remote season change (INPUT ON=winter, INPUT OFF=summer)
2=remote On/Off (INPUT ON=OFF, INPUT OFF=ON)
3=non-occupied holiday (INPUT ON=Occupied)
4=economy/boost (INPUT ON = economy activated)
5=forced contact presence (INPUT ON=forced control with base setpoint)
6=frost protection alarm contact (INPUT ON=frost protection active)
7=generic alarm contact (INPUT ON=generic alarm)
8=condensation contact (INPUT ON=condensate alarm)
9=generic filter contact (INPUT ON=generic filter alarm)
10=supply filter contact (INPUT ON=supply filter alarm)
11=extraction filter contact (INPUT ON=extractor filter alarm)
12=stop all alarm contact (INPUT ON=stop all alarm)
13=fan alarm contact (INPUT ON=fan alarm)
14=frost protection alarm contact of heat exchanger (INPUT ON=frost
protection heat exchanger active)
017
0
0
14
R/W
9134
DIG_INPUT2_LOG
→
Digital input contact logic 2:
0=normally open (open = INPUT OFF, closed = INPUT ON)
1=normally closed (closed = INPUT OFF, open = INPUT ON)
018
0
0
1
R/W