Operation with on/off bypass damper and on/off cooling valve:
Do following settings:
-
170
=1 or 3 (authorization of free cooling regardless the working season), or
170
=4 or 6 (authorization of free cooling in cool
-
ing mode only),
- do the regulation on room sensor (internal or remote sensor)
001
=0;
in case the remote sensor is used set an analogue input as remote sensor
019
=1 (AI1) or
021
=1 (AI2) or
023
=1 (AI3)),
- set an analogue input as external sensor
019
=3 (AI1) or
021
=3 (AI2) or
023
=3 (AI3),
- on/off bypass damper for heat exchanger
010
=2,
011
=1 and
012
=1 ,
025
=13 (DO1) or
026
=13 (DO2) or
027
=13 (DO3) or
028
=13 (DO4) or
029
=13 (DO5),
- on/off cooling valve
003
=2 and
025
=5 (DO1) or
026
=5 (DO2) or
027
=5 (DO3) or
028
=5 (DO4) or
029
=5 (DO5),
or on/off mixed-use valve in cooling
002
=4,
003
=2 and
025
=6 (DO1) or
026
=6 (DO2) or
027
=6 (DO3) or
028
=6 (DO4) or
029
=6
(DO5).
100%
0%
Treg
114
WHS
114
/2
100%
0%
Treg
116
WCS
116
/2
178
178
100%
0%
Treg
122
WHS
122
/2
100%
0%
Treg
122
122
/2
WCS
178
178
100%
0%
Treg
WHS
123
100%
0%
Treg
WCS
123
178
178
100%
0%
Treg
WCS
178
100%
0%
Treg
WHS
178
Treg: control temperature
WCS: cooling operation setpoint
122
: hysteresis for on/off output
178
hysteresis regulation free heating/cooling
solid curve: on/off damper output
dashed curve: modulating cooling valve output
In the presence of free cooling conditions:
if Treg > WCS the on/off damper is activated.
if Treg <= (WCS -
178
) the damper is deactivated.
if Treg > (WCS +
122
) the cooling valve is activated.
if Treg <= (WCS +
122
/2) the cooling valve is deactivated.
Operation with modulating damper and on/off cooling valve:
Do following settings:
-
170
=1 or 3 (authorization of free cooling regardless the working season), or
170
=4 or 6 (authorization of free cooling in cool
-
ing mode only),
- do the regulation on room sensor (internal or remote sensor)
001
=0;
in case the remote sensor is used set an analogue input as remote sensor
019
=1 (AI1) or
021
=1 (AI2) or
023
=1 (AI3)),
- set an analogue input as external sensor
019
=3 (AI1) or
021
=3 (AI2) or
023
=3 (AI3),
- external modulating damper regulated on free c/h:
010
=3,
011
=1 or 2 and
030
=9 (AO1) or
031
=9 (AO2) or
032
=9 (AO3),
or modulating bypass for heat exchanger
010
=4,
011
=1 and
012
=1,
030
=13 (AO1) or
031
=13 (AO2) or
032
=13 (AO3).
- on/off cooling valve
003
=2 and
025
=5 (DO1) or
026
=5 (DO2) or
027
=5 (DO3) or
028
=5 (DO4) or
029
=5 (DO5),
or on/off mixed-use valve in cooling
002
=4,
003
=2 and
025
=6 (DO1) or
026
=6 (DO2) or
027
=6 (DO3) or
028
=6 (DO4) or
029
=6
(DO5).
100%
0%
Treg
114
WHS
114
/2
100%
0%
Treg
116
WCS
116
/2
100%
0%
Treg
114
WHS
114
/2
100%
0%
Treg
116
WCS
116
/2
100%
0%
Treg
122
WHS
122
/2
100%
0%
Treg
122
WCS
122
/2
100%
0%
Treg
122
WHS
122
/2
100%
0%
Treg
122
WCS
122
/2
100%
0%
Treg
WHS
123
178
100%
0%
Treg
WHS
123
178
100%
0%
Treg
WCS
123
178
100%
0%
Treg
WCS
123
178
Treg: control temperature
WCS: cooling operation setpoint
122
: hysteresis for on/off output
solid curve: modulating damper output
dashed curve: on/off cooling valve output
If temperature of regulation sensor rises above WCS, the modulating damper in the presence of free cooling conditions goes
from the minimum opening position (parameter
164
) to the maximum opening position (parameter
165
) in the band defined by