Parameter Description
Default
Min
Max
018
Digital input 2 contact logic:
0=normally open (open = INPUT OFF, closed = INPUT ON)
1=normally closed (closed = INPUT OFF, open = INPUT ON)
0
0
1
019
Analogue input 1 function:
0=not used
1=remote control sensor
2=supply sensor
3=external sensor
4=frost protection heat exchanger sensor
8=season change remote contact (INPUT ON=winter, INPUT OFF=summer)
9=remote On/Off (INPUT ON=OFF, INPUT OFF=ON)
10=non-occupied/holiday (INPUT ON=occupied)
11=economy/boost (INPUT ON=economy activated)
12=forced presence contact (INPUT ON = forced -> control with base setpoint)
13=frost protection (INPUT ON= frost protection alarm)
14=generic alarm (INPUT ON=generic alarm)
15=condensation contact (INPUT ON=condensation alarm)
16=generic filter contact (INPUT ON=generic filter alarm)
17=supply filter contact (INPUT ON=supply filter alarm)
18=extract filter contact (INPUT ON=extract filter alarm)
19=stop all alarm contact (INPUT ON=stop all alarm)
20=fan alarm contact (INPUT ON=fan alarm)
21=frost protection heat exchanger contact (INPUT ON=frost protection heat exchanger alarm)
0
0
21
020
Logic for analogue input 1 (only with
019
=8 to 21):
0=normally open (open = INPUT OFF, closed = INPUT ON)
1=normally closed (closed = INPUT OFF, open = INPUT ON)
0
0
1
021
Analogue input 2 function:
0=not used
1=remote control sensor
2=supply sensor
3=external sensor
4=frost protection heat exchanger sensor
8=season change remote contact (INPUT ON=winter, INPUT OFF=summer)
9=remote On/Off (INPUT ON=OFF, INPUT OFF=ON)
10=non-occupied/holiday (INPUT ON=occupied)
11=economy/boost (INPUT ON=economy activated)
12=forced presence contact (INPUT ON = forced -> control with base setpoint)
13=frost protection (INPUT ON= frost protection alarm)
14=generic alarm (INPUT ON=generic alarm)
15=condensation contact (INPUT ON=condensation alarm)
16=generic filter contact (INPUT ON=generic filter alarm)
17=supply filter contact (INPUT ON=supply filter alarm)
18=extract filter contact (INPUT ON=extract filter alarm)
19=stop all alarm contact (INPUT ON=stop all alarm)
20=fan alarm contact (INPUT ON=fan alarm)
21=frost protection heat exchanger contact (INPUT ON=frost protection heat exchanger alarm)
0
0
21
022
Logic for analogue input 2 (only with
021
=8 to 21):
0=normally open (open = INPUT OFF, closed = INPUT ON)
1=normally closed (closed = INPUT OFF, open = INPUT ON)
0
0
1
023
Analogue input 3 function:
0=not used
1=remote control sensor
2=supply sensor
3=external sensor
4=frost protection heat exchanger sensor
5=input 0...10 V for air quality sensor (excludes AHU-3xxSx1 models)
6=0....10 V input for humidity sensor (excludes AH-3xxSx1 models)
7=0...10 V input for pressure transmitter (excludes AHU-3xxSx1 models)
8=season change remote contact (INPUT ON=winter, INPUT OFF=summer)
9=remote On/Off (INPUT ON=OFF, INPUT OFF=ON)
10=non-occupied/holiday (INPUT ON=occupied)
11=economy/boost (INPUT ON=economy activated)
12=forced presence contact (INPUT ON = forced -> control with base setpoint)
13=frost protection (INPUT ON= frost protection alarm)
14=generic alarm (INPUT ON=generic alarm)
15=condensation contact (INPUT ON=condensation alarm)
16=generic filter contact (INPUT ON=generic filter alarm)
17=supply filter contact (INPUT ON=supply filter alarm)
18=extract filter contact (INPUT ON=extract filter alarm)
19=stop all alarm contact (INPUT ON=stop all alarm)
20=fan alarm contact (INPUT ON=fan alarm)
21=frost protection heat exchanger contact (INPUT ON=frost protection heat exchanger alarm)
0
0
21