3. Analogue input 3 (
AI3
):
Parameter
Logic
023
=0
Sensor not used
023
=1
Remote regulation
sensor
The
AI3
sensor is used together with the internal sensor to obtain the final room regulation
temperature according to the parameter
106
(see
“8. Control sensors” page 16
:
023
=2
Supply sensor
The
AI3
sensor is used as a limit sensor for fixed-point regulation with limits (
125
and/or
127
not equal to 0), or as a regulation sensor for the valves (
001
=1), or as a regulation sensor in
the cascade regulation (
014
=2).
023
=3
External sensor
The
AI3
sensor is used for the compensation (
130
not equal to 0)
023
=4
Frost protection
heat exchanger
sensor
The
AI3
sensor is used as a frost protection
heat exchanger
sensor
023
=5
Air quality input
0..10V
Jumper JP1 = position “3-2”.
Setting
023
=5, automatically
206
=0,
207
=2000,
208
=0
023
=6
Humidity transmitter
input 0..10V
Jumper JP1 = position “3-2”.
Setting
023
=6, automatically
206
=0,
207
=100,
208
=1
023
=7
Pressure transmitter
input 0..10V
Jumper JP1 = position “3-2”.
Set the scale of the connected pressure transmitter
206
,
207
, and set
208
=0
023
=8
Remote season
change contact
024
=
0
1
Summer
Winter
023
=9
Remote on/off
contact
024
=
0
1
On
Off
023
=10
Non-occupied/
holiday contact
024
=
0
1
“Non-occupied holiday” mode
“Occupied” mode
023
=11
Energy savings
remote contact
024
=
0
1
No economy/boost mode
Economy/boost mode
023
=12
Forced presence
contact
024
=
0
1
No forced presence
Modes with forced presence
023
=13
Heat frost protection
battery contact
024
=
0
1
Frost protection off
Frost protection on
023
=14
Generic alarm
contact
024
=
0
1
No alarm
Alarm active
023
=15
Condensation alarm
contact
024
=
0
1
No condensation
Condensation alarm
023
=16
Generic filter alarm
contact
024
=
0
1
No generic filter alarm
Generic filter alarm