• Free cooling in winter:
In some cases, it may be necessary to cool a room even in the heating season when, for example, a place is very crowded
and the temperature rises too high.
Operation with modulating damper:
Do following settings:
-
170
=1 or 3 (authorization of free cooling regardless the season),
- do the regulation on room sensor (internal or remote sensor)
001
=0;
in case the remote sensor is used set an analogue input as remote sensor
019
=1 (AI1) or
021
=1 (AI2) or
023
=1 (AI3)),
- set an analogue input as external sensor
019
=3 (AI1) or
021
=3 (AI2) or
023
=3 (AI3),
- external modulating damper regulated on free c/h:
010
=3,
011
=1 or 2 and
030
=9 (AO1) or
031
=9 (AO2) or
032
=9 (AO3),
or modulating bypass for heat exchanger
010
=4,
011
=1 and
012
=1,
030
=13 (AO1) or
031
=13 (AO2) or
032
=13 (AO3).
100%
0%
Treg
114
WHS
114
/2
100%
0%
Treg
116
WCS
116
/2
100%
0%
Treg
114
WHS
114
/2
100%
0%
Treg
116
WCS
116
/2
100%
0%
Treg
122
WHS
122
/2
100%
0%
Treg
122
WCS
122
/2
100%
0%
Treg
122
WHS
122
/2
100%
0%
Treg
122
WCS
122
/2
100%
0%
Treg
WHS
123
178
100%
0%
Treg
WHS
123
178
100%
0%
Treg
WCS
123
178
100%
0%
Treg
WCS
123
178
Treg: control temperature
WHS: heating operation setpoint
123
: neutral zone
178
: hysteresis for control of free heating/cooling
If the control temperature rises above WHS +
123,
the modulating damper in the presence of free cooling goes from the
minimum opening position (parameter
164
) to the maximum opening position (parameter
165
) in the band defined by the
parameter
178
.
Note: if external modulating damper is used, the presence of the heating battery is mandatory:
heating valve on/off
002
=4 and
025
=4 (DO1) or
026
=4 (DO2) or
027
=4 (DO3) or
028
=4 (DO4) or
029
=4 (DO5),
or electrical resistance on/off
002
=3 and
025
=7 (DO1) or
026
=7 (DO2) or
027
=7 (DO3) or
028
=7 (DO4) or
029
=7 (DO5),
or on/off mixed-use valve in heating
002
=4,
003
=2 and
025
=6 (DO1) or
026
=6 (DO2) or
027
=6 (DO3) or
028
=6 (DO4) or
029
=6
(DO5),
or modulating heating valve
002
=2 and
030
=3 (AO1) or
031
=3 (AO2) or
032
=3 (AO3),
or modulating mixed-use valve in heating
002
=2
003
=1 and
030
=5 (AO1) or
031
=5 (AO2) or
032
=5 (AO3),
or modulating electrical resistance
002
=1 and
030
=6 (AO1) or
031
=6 (AO2) or
032
=6 (AO3).
If modulating bypass damper for heat exchanger is used, the presence of the heating battery is not mandatory.
Operation with on/off damper:
Do following settings:
-
170
=1 or 3 (authorization of free cooling regardless the season),
- do the regulation on room sensor (internal or remote sensor)
001
=0;
in case the remote sensor is used set an analogue input as remote sensor
019
=1 (AI1) or
021
=1 (AI2) or
023
=1 (AI3)),
- set an analogue input as external sensor
019
=3 (AI1) or
021
=3 (AI2) or
023
=3 (AI3),
- external on/off damper controlled by free cooling/heating:
010
=1 and
025
=11 (DO1) or
026
=11 (DO2) or
027
=11 (DO3) or
028
=11 (DO4) or
029
=11 (DO5),
100%
0%
Treg
114
WHS
114
/2
100%
0%
Treg
116
WCS
116
/2
100%
0%
Treg
114
WHS
114
/2
100%
0%
Treg
116
WCS
116
/2
100%
0%
Treg
122
WHS
122
/2
100%
0%
Treg
122
WCS
122
/2
100%
0%
Treg
122
WHS
122
/2
100%
0%
Treg
122
WCS
122
/2
100%
0%
Treg
WHS
123
178
100%
0%
Treg
WHS
123
178
100%
0%
Treg
WCS
123
178
100%
0%
Treg
WCS
123
178
Treg: control temperature
WHS: heating operation setpoint
123
: neutral zone
178
: hysteresis for control of free heating/cooling