• Maximum limit:
To enable the high limit in cooling mode, set
127
=1.
To enable the high limit in heating mode, set
127
=2.
To enable the high limit in heating and cooling mode, set
127
=3.
To disable this function, set
127
=0.
High limit in heating mode with modulating control:
Tlim
126
129
100
0
Val_lim_min_H
Tlim
128
129
100
0
Val_lim_max_H
Tlim
126
129
100
0
Val_lim_min_C
Tlim
128
129
100
0
Val_lim_max_C
Te
132
133
0
Set_comp_heat
131
134
Te
136
137
0
Set_comp_cool
135
138
Te
132
133
0
Set_comp_heat
131
134
Te
136
137
0
Set_comp_cool
135
138
Hlim
148
149
100
0
Lim_max_hum
Hlim
146
149
100
0
Lim_min_dehum
ON
OFF
Hlim
149
Lim_min_dehum
146
DOx
ON
OFF
Hlim
149
Lim_max_hum
148
DOx
Val_lim_max_H: theoretical value of the high limit output in heating mode
Tlim: temperature of the supply sensor
128
: setpoint of high limit
129
: proportional limit band
When active, if the supply temperature goes above the maximum supply setpoint
128
, the heating valve is controlled consider
-
ing the lowest value between the theoretical output of the heating control and the theoretical value of the Val_lim_max_H limit.
Above
128
the
icon is displayed and on the alarms page, the message
LI-H
is displayed.
High limit in heating mode with on-off control:
Speed
100%
152
Extractor fan
10V
Volt
ON
OFF
Tlim
129
Val_lim_max_H
128
126
Control temperature
Supply setpoint
128
118
107
126
Control temperature
Supply setpoint
128
118
108
126
Control temperature
Supply setpoint
128
118
109
ON
OFF
Tlim
129
Val_lim_min_H
126
150
153
151
Supply fan
Speed
100%
150
Extractor fan
10V
Volt
152
151
153
Supply fan
Speed 1
Ambient CO2
Fan
Speed 3
I56
I55
Outdoor temp
Setpoint offset
I34
I32
I35
I38
I39
I33
I36
I37
Supply temp.
OUTH
100%
HEATING
modulating
114
116
123
Supply
setpoint
COOLING
modulating
0%
Treg
HEATING
COOLING
100%
0%
Treg
122
124
WCS
100%
0%
Treg
OUT
124
WCS
114
AOx
DOx
DOx
126
Control temperature
Supply setpoint
128
118
Set_reg
Control temperature
HEATING
I24
COOLING
Set_comp
Speed 1
Humidity
Fan
Speed 3
I42
I41
AOx
ON
OFF
Tlim
129
Val_lim_max_C
128
ON
OFF
Tlim
129
Val_lim_min_C
126
DOx
DOx
OUT
WHS
WCS
Treg
HEATING
COOLING
109
I23
I23
OUTC
Supply temp.
OUTH
100%
Modulating
HEATING
114
123/2
Supply setpoint
0%
Supply temp.
100%
116
Supply setpoint
Modulating
COOLING
0%
OUTC
123/2
Val_lim_max_H: theoretical value of the high limit output in heating mode
Tlim: temperature of the supply sensor
128
: setpoint of high limit
129
: proportional limit band
When active, if the supply temperature goes above the maximum supply setpoint
128 +
(proportional band
129
), the on/off
output in heating mode is controlled considering the lowest value between the theoretical on/off output of the heating control
and the theoretical value of the Val_lim_min_H limit.
Above
128
+
129
the
icon is displayed and on the alarms page, the message
LI-H
is displayed.