48/160
AB Industrietechnik srl – Via Julius Durst, 70 – 39042 BRESSANONE (BZ) Italy – Tel: +39 0472/830626 – [email protected] – www.industrietechnik.it
and the post-heating setpoint 179 independently of the priority.
Temperature setpoint reached, control of humidity:
Temperature
request
Humidity request
Heating battery
Cooling/
dehumidification
battery
Post-heating
battery
Humidifier
Heating achieved
Humidification
OFF
OFF
OFF
ON
Heating achieved
Dehumidification
OFF
007=0:
ON
(controlled by the
dehumidification
signal)
ON
(controlled by the
supply sensor
and post-heating
sensor179)
OFF
007=1 or 2:
ON
(dehumidification
using the
modulating or on/off
dehumidifier)
Cooling achieved
Humidification
OFF
OFF
OFF
ON
Cooling achieved
Dehumidification
OFF
007=0:
ON
(controlled by the
dehumidification
signal)
ON
(controlled by the
supply sensor and the
post setpoint 179)
OFF
007=1 or 2:
ON
(dehumidification
using the
modulating or on/off
dehumidifier)
(*) if
005=2, the post-heating battery has the function of additional heating battery. It is controlled based on the supply sensor
and the post-heating setpoint 179 independently of the priority.