130/160
AB Industrietechnik srl – Via Julius Durst, 70 – 39042 BRESSANONE (BZ) Italy – Tel: +39 0472/830626 – [email protected] – www.industrietechnik.it
Parameter
Logic
021
=13
Heat frost protection
battery contact
022
=
0
1
Frost protection off
Frost protection on
021
=14
Generic alarm
contact
022
=
0
1
No alarm
Alarm active
021
=15
Condensation
alarm contact
022
=
0
1
No condensation
Condensation alarm
021
=16
Generic filter
alarm contact
022
=
0
1
No generic filter alarm
Generic filter alarm
021
=17
Supply filter
alarm contact
022
=
0
1
No supply filter alarm
Supply filter alarm
021
=18
Extraction filter
alarm contact
022
=
0
1
No extraction filter alarm
Extraction filter alarm
021
=19
Stop all alarm
contact
022
=
0
1
No stop all alarm
Stop all alarm
021
=20
Fan alarm contact
022
=
0
1
No fan alarm
Fan alarm
021
=21
Frost protection
heat exchanger
alarm contact
022
=
0
1
No frost protection heat exchanger
Frost protection heat exchanger alarm
For configurations
021
=8 to 21, the analogue input 2 is used as a digital input. The contact is considered closed if it is
short-circuited at the analogue input. The contact is considered open if there is no connection.