147/160
AB Industrietechnik srl – Via Julius Durst, 70 – 39042 BRESSANONE (BZ) Italy – Tel: +39 0472/830626 – [email protected] – www.industrietechnik.it
Register Description
Default
Min
Max
R/W
9143
DIG_OUTPUT3_FUNC
→
Digital output operation 3 (models AHU-0xxSx1,
AHU-1xxSx1 excluded)
0=not used
1=speed 1 for on/off fan
2=speed 2 for on/off fan
3=speed 3 for on/off fan
4=heating valve
5=cooling valve
6=mixed-use valve
7=electrical resistance
8=post-heating valve
9=post-heating electrical resistance
10=authorisation for humidifier
11=external regulated damper
12=external damper
13=bypass damper for cross-flow heat exchanger
14=double battery heat exchanger or on/off rotary heat exchanger
15=pre-heating electrical resistance for heat exchanger
16=on/off humidifier
17=on/off dehumidifier
18=fan alarm output
19=relay for EC motors
20=bypass damper for cross-flow heat exchanger (based on free c/h only)
027
0
0
20
R/W
9144
DIG_OUTPUT4_FUNC
→
Digital output operation 4 (models AHU-0xxSx1,
AHU-1xxSx1, AHU-2xxSx1, AHU-3xxSx1 excluded)
0=not used
1=speed 1 for on/off fan
2=speed 2 for on/off fan
3=speed 3 for on/off fan
4=heating valve
5=cooling valve
6=mixed-use valve
7=electrical resistance
8=post-heating valve
9=post-heating electrical resistance
10=authorisation for humidifier
11=external regulated damper
12=external damper
13=bypass damper for cross-flow heat exchanger
14=double battery heat exchanger or on/off rotary heat exchanger
15=pre-heating electrical resistance for heat exchanger
16=on/off humidifier
17=on/off dehumidifier
18=fan alarm output
19=relay for EC motors
20=bypass damper for cross-flow heat exchanger (based on free c/h only)
028
0
0
20
R/W
9145
DIG_OUTPUT5_FUNC
→
Digital output operation 5 (models AHU-0xxSx1,
AHU-1xxSx1, AHU-2xxSx1, AHU-3xxSx1 excluded)
0=not used
1=speed 1 for on/off fan
2=speed 2 for on/off fan
3=speed 3 for on/off fan
4=heating valve
5=cooling valve
6=mixed-use valve
7=electrical resistance
8=post-heating valve
9=post-heating electrical resistance
10=authorisation for humidifier
11=external regulated damper
12=external damper
13=bypass damper for cross-flow heat exchanger
14=double battery heat exchanger or on/off rotary heat exchanger
15=pre-heating electrical resistance for heat exchanger
16=on/off humidifier
17=on/off dehumidifier
18=fan alarm output
19=relay for EC motors
20=bypass damper for cross-flow heat exchanger (based on free c/h only)
029
0
0
20
R/W