139/160
AB Industrietechnik srl – Via Julius Durst, 70 – 39042 BRESSANONE (BZ) Italy – Tel: +39 0472/830626 – [email protected] – www.industrietechnik.it
Register Description
Min
Max
R/W
10053
FLAG_STATE_EXCHANGER
→
heat exchanger status
0=heat recovery stopped
1=heat recovery in progress
2=frost protection alarm present in the heat exchanger
3=heat exchanger stopped for free cooling or free heating
0
3
R
10054
FLAG_GEN_ALARM
→
general alarm status
0=no alarm
1=general alarm
0
1
R
10055
FLAG_ALARM_CONDENSATION
→
condensation alarm status
0=no condensation alarm
1=condensation alarm
0
1
R
10056
FLAG_GENERAL_FILTER_ALARM
→
filter alarm status
0=no filter alarm
1=filter alarm
0
1
R
10057
FLAG_SUPPLY_FILTER_ALARM
0=no supply fan filter alarm
1=filter alarm for supply fan
0
1
R
10058
FLAG_EXTRACT_FILTER_ALARM
0=no filter alarm for extract fan
1=filter alarm for extract fan
0
1
R
10059
FLAG_ALARM_STOP_ALL
0=no alarm stop all
1=stop all alarm
0
1
R
10060
FLAG_ALARM_VENTILATION
→
fan alarm status
0=no alarm for fan
1=fan alarm
0
1
R
from
10061 to
10077
Reserved addresses
R
10078
TYPE_OF_HARDWARE
0=1 digital output, 3 analogue outputs
1=2 digital outputs, 2 analogue outputs
2=3 digital outputs, 1 analogue output
3=3 digital outputs, 2 analogue outputs
4=5 digital outputs
0
4
R
10079
TYPE_COMMUNICATION
0=not present
1=MODBUS
0
1
R
10080
RTC_PRESENCE
0=not present
1=present
0
1
R
10081
HUM_PRESENCE
0=not present
1=present
0
1
R
10082
IR_PRESENCE
0=not present
1=present
0
1
R
10083
FORCED_OUTPUTS_KEY
→
key to select forced outputs
0 / 26312
26367
R/W
from
10084 to
10085
Reserved addresses
R