Parameter Description
Default
Min
Max
024
Logic for analogue input 3 (only with
023
=8 to 21):
0=normally open (open = INPUT OFF, closed = INPUT ON)
1=normally closed (closed = INPUT OFF, open = INPUT ON)
0
0
1
025
Digital output function 1:
0=not used
1=speed 1 for on/off fan
2=speed 2 for on/off fan
3=speed 3 for on/off fan
4=heating valve
5=cooling valve
6=mixed-use valve
7=electrical resistance
8=post-heating valve
9=post-heating electrical resistance
10=authorisation for humidifier
11=external regulated damper
12=external damper
13=bypass damper for heat exchanger
14=double battery heat exchanger or on/off rotary heat exchanger
15=pre-heating electrical resistance for heat exchanger
16=on/off humidifier
17=on/off dehumidifier
18=fan alarm output
19=relay for EC motors
20=bypass damper for cross-flow heat exchanger (based on free c/h only)
0
0
20
026
Digital output function 2 (models AHU-0xxSx1 excluded)
0=not used
1=speed 1 for on/off fan
2=speed 2 for on/off fan
3=speed 3 for on/off fan
4=heating valve
5=cooling valve
6=mixed-use valve
7=electrical resistance
8=post-heating valve
9=post-heating electrical resistance
10=authorisation for humidifier
11=external regulated damper
12=external damper
13=bypass damper for heat exchanger
14=double battery heat exchanger or on/off rotary heat exchanger
15=pre-heating electrical resistance for heat exchanger
16=on/off humidifier
17=on/off dehumidifier
18=fan alarm output
19=relay for EC motors
20=bypass damper for cross-flow heat exchanger (based on free c/h only)
0
0
20
027
Digital output function 3 (models AHU-0xxSx1, AHU-1xxSx1 excluded)
0=not used
1=speed 1 for on/off fan
2=speed 2 for on/off fan
3=speed 3 for on/off fan
4=heating valve
5=cooling valve
6=mixed-use valve
7=electrical resistance
8=post-heating valve
9=post-heating electrical resistance
10=authorisation for humidifier
11=external regulated damper
12=external damper
13=bypass damper for heat exchanger
14=double battery heat exchanger or on/off rotary heat exchanger
15=pre-heating electrical resistance for heat exchanger
16=on/off humidifier
17=on/off dehumidifier
18=fan alarm output
19=relay for EC motors
20=bypass damper for cross-flow heat exchanger (based on free c/h only)
0
0
20