WindO/I-NV4 User’s Manual
13-39
4 Using Data and Detected Alarms
13
Alarm Log Function
4.4 Saving the Data as a CSV File
●
Saving the Data as a CSV File
The Alarm Log data can be saved to the external memory device
as a CSV file or uploaded to a computer.
The procedure to save the data is as follows.
• To save the data to an external memory device, click
Alarm Log
on the WindO/I-NV4
Configuration
tab to open
the Alarm Log Settings dialog box. Select an output method check box on the
External Memory Device
tab and
configure the items. The data can be saved to the External Memory Device folder on the external memory device.
For details, refer to “External Memory Device Tab” on page 13-20.
• To upload the data to a computer, click on
▼
to the right of
(Upload) on the toolbar in Data File Manager, and
then click the
Upload All Log Data
or
Upload Alarm Log Data
to open the Browser For Folder dialog box.
Specify the location to save the file and click
OK
to save the file to the specified folder. For details, refer to the Data
File Manager User's Manual.
●
Data Structure and Output Example
The data structure for files output with batch output and real time output is different.
■
Batch
Batch output shows the recovery and confirmation time for an alarm that has occurred on a single line.
The data structure of files output with batch output is as follows. Bold items are replaced by the Alarm Log settings,
the sampled data, the running project name, and WindO/I-NV4 version number.
*1 SD memory card for HG5G/4G/3G/2G-V, HG4G/3G and HG2G-5F, USB flash drive for HG2G-5T and HG1G/1P
Headers
"Project Name","
Project name
","
Version number
"
"File Type","
Log type
"
Blank row
Title row
"Ch.No.","Message","Occurrence Time","Recovery Time","Confirmation Time"
Data row
"
Channel number
","
Message
","
MM/DD/YYYY hh:mm:ss
","
MM/DD/YYYY hh:mm:ss
",
"
MM/DD/YYYY hh:mm:ss
"
·
·
·
Output example
Data size of each row
"Project Name","Dimmer Console","V4.50"
- 41 bytes
"File Type","Alarm Log Data"
- 30 bytes
- 2 bytes
"Ch.No.","Message","Occurrence Time","Recovery Time","Confirmation Time"
- 74 bytes
" 1-0","Voltage drop"," 08/11/2011 14:46:12"," 08/11 14:46:13"," 08/11
14:46:16"
- 82 bytes
" 1-1","Temperature abnormal"," 08/11/2011 14:47:18"," 08/11 14:47:19",
" 08/11 14:47:20"
- 90 bytes
·
·
·
Summary of Contents for MICRO/I HG4G-CJT22 F-B Series
Page 1: ...B 1701 11 User s Manual ...
Page 26: ...Preface 25 WindO I NV4 User s Manual ...
Page 106: ...5 WindO I NV4 Common Operations and Settings 2 74 WindO I NV4 User s Manual ...
Page 254: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual ...
Page 362: ...5 Screen Restrictions 5 28 WindO I NV4 User s Manual ...
Page 402: ...3 Text 7 30 WindO I NV4 User s Manual ...
Page 574: ...9 Potentiometer 8 172 WindO I NV4 User s Manual ...
Page 1052: ...4 Using the Data 15 22 WindO I NV4 User s Manual ...
Page 1170: ...6 Important Notes 20 60 WindO I NV4 User s Manual ...
Page 1200: ...5 Restrictions 22 18 WindO I NV4 User s Manual ...
Page 1260: ...5 Editing User Accounts on the MICRO I 23 60 WindO I NV4 User s Manual ...
Page 1322: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual ...
Page 1414: ...4 E mail Function 28 66 WindO I NV4 User s Manual ...
Page 1554: ...3 Settings 34 14 WindO I NV4 User s Manual ...
Page 1642: ...2 Handling Problems 36 6 WindO I NV4 User s Manual ...
Page 1652: ...5 Text Alignment A 10 WindO I NV4 User s Manual ...
Page 1664: ...Index 12 WindO I NV4 User s Manual ...