7 BACnet Communication
3-100
WindO/I-NV4 User’s Manual
●
Subscribed COV (COV) function
In the COV (Change Of Value) function, the MICRO/I monitors an object for which a report request has been received
from a BACnet device. Then when Present_Value or Status_Flags has changed, the MICRO/I notifies the BACnet
device of the change.
The properties of objects that correspond to the COV function and the timing of when to provide notification of
changes are given as follows.
*1 For example, the following diagram shows when a report request is received from a BACnet device and AI-10 (Analog Input
object, instance number 10) has the status in the following table.
Object
Properties
Timing to Provide Notification of Change
Analog Input
Analog Output
Analog Value
Present_Value
Status_Flags
Notification of change is provided when (1) or (2) as follows.
(1)
When
Present_Value
has changed to a value greater than or equal to the value
set for
COV
_Increment (starting point is from when the previous COV
notification was sent)
(2) When any of the bits in Status_Flags have changed
Binary Input
Binary Output
Binary Value
Present_Value
Status_Flags
Notification of change is provided when (1) or (2) as follows.
(1) When
Present_Value
has changed
(2) When any of the bits in Status_Flags have changed
Notification may not be provided for changes in values that are faster than the synchronization cycle of
objects and device addresses.
AI-10 Properties
Value
Present_Value
10.0
COV
_Increment
3.0
BACnet device
MICRO/I
Report request
COV notification
transmission
(To report requester)
Present_Value of AI-10
has changed to 15.0.
COV notification
transmission
Present_Value of AI-10
has changed to 18.5.
Present_Value of AI-10: 10.0
COV_Increment: 3.0
Present_Value of AI-10 has changed to 15.0
(Change in Present_Value (5.0) > COV_Increment (3.0))
This change corresponds to timing to provide notification of change (1).
Change in Present_Value = Present value - Value when report request
was received = 15.0 - 10.0 = 5.0
Because COV_Increment = 3.0,
change in present value ≥ COV_Increment has been satisfied.
Present_Value of AI-10 has changed to 17.5
(Change in Present_Value (2.5) > COV_Increment (3.0))
Change in Present_Value = Present value - Value when previous
COV notification was transmitted = 17.5 - 15.0 = 2.5
Change in Present_Value < COV_Increment, and the condition
for timing to provide notification of change (1) is not satisfied.
Therefore, COV notification is not sent.
Present_Value of AI-10 has changed to 18.5
(Change in Present_Value (3.5) > COV_Increment (3.0))
This change corresponds to timing to provide notification of change (1).
Change in Present_Value = Present value - Value when previous
COV notification was transmitted = 18.5 - 15.0 = 3.5
Because COV_Increment = 3.0,
Change in Present Value ≥ COV_Increment has been satisfied.
Summary of Contents for MICRO/I HG4G-CJT22 F-B Series
Page 1: ...B 1701 11 User s Manual ...
Page 26: ...Preface 25 WindO I NV4 User s Manual ...
Page 106: ...5 WindO I NV4 Common Operations and Settings 2 74 WindO I NV4 User s Manual ...
Page 254: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual ...
Page 362: ...5 Screen Restrictions 5 28 WindO I NV4 User s Manual ...
Page 402: ...3 Text 7 30 WindO I NV4 User s Manual ...
Page 574: ...9 Potentiometer 8 172 WindO I NV4 User s Manual ...
Page 1052: ...4 Using the Data 15 22 WindO I NV4 User s Manual ...
Page 1170: ...6 Important Notes 20 60 WindO I NV4 User s Manual ...
Page 1200: ...5 Restrictions 22 18 WindO I NV4 User s Manual ...
Page 1260: ...5 Editing User Accounts on the MICRO I 23 60 WindO I NV4 User s Manual ...
Page 1322: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual ...
Page 1414: ...4 E mail Function 28 66 WindO I NV4 User s Manual ...
Page 1554: ...3 Settings 34 14 WindO I NV4 User s Manual ...
Page 1642: ...2 Handling Problems 36 6 WindO I NV4 User s Manual ...
Page 1652: ...5 Text Alignment A 10 WindO I NV4 User s Manual ...
Page 1664: ...Index 12 WindO I NV4 User s Manual ...