WindO/I-NV4 User’s Manual
13-19
3 Alarm Log Settings Dialog Box
13
Alarm Log Function
■
Channel Settings
The trigger condition for the channel is configured here.
Alarm function:
Selects whether or not to use the alarm function.
Enable:
Monitors the state of the device address configured for the channel and samples
the alarm information.
Disable: Does not monitor the state of the device address. No Alarm Log data is created.
NO/NC:
Selects the alarm detection condition.
NO:
The alarm occurs when the monitored bit changes from 0 to 1.
NC:
The alarm occurs when the monitored bit changes from 1 to 0.
Lock/Unlock:
Selects whether or not to automatically recover based on the state of the monitored bit.
Lock:
Even if the monitored bit returns the normal state, the alarm remains active until
the key button
CHECK
is pressed.
Unlock:
The alarm is automatically recovered from based on the bit state when the
monitored bit returns the normal state.
Example:
NO/NC
is
NO
Press
CHECK
Record confirmaon me
Record recovery me
Record occurrence me
Unlock
Record confirmaon me
Record recovery me
No operaon
Record occurrence me
Lock
0
1
0
1
Monitored bit
Alarm occurred
The display on the Alarm List Display disappears when the alarm is recovered from, regardless of the
Lock/
Unlock
setting. To keep displaying the alarm until
CHECK
is pressed, use the Alarm Log Display.
Text ID:
To use text registered in Text Manager as the message to display when an alarm occurs,
select this check box and specify the Text Manager ID number to use as the message.
Number of blocks x 16 (number of channels) text IDs are used starting from the set ID
number.
Click
to open Text Manager where you can edit the text.
Text:
Shows the text for the specified text ID.
Reference Screen Number: Specifies the screen number (1 to 3000) to display when the key button
Ref.
is pressed.
Number of blocks x 16 (number of channels) screens are used starting from the screen
number.
This option can only be configured when
Base Screen
or
Popup Screen
is selected in
Reference Screen
.
Summary of Contents for MICRO/I HG4G-CJT22 F-B Series
Page 1: ...B 1701 11 User s Manual ...
Page 26: ...Preface 25 WindO I NV4 User s Manual ...
Page 106: ...5 WindO I NV4 Common Operations and Settings 2 74 WindO I NV4 User s Manual ...
Page 254: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual ...
Page 362: ...5 Screen Restrictions 5 28 WindO I NV4 User s Manual ...
Page 402: ...3 Text 7 30 WindO I NV4 User s Manual ...
Page 574: ...9 Potentiometer 8 172 WindO I NV4 User s Manual ...
Page 1052: ...4 Using the Data 15 22 WindO I NV4 User s Manual ...
Page 1170: ...6 Important Notes 20 60 WindO I NV4 User s Manual ...
Page 1200: ...5 Restrictions 22 18 WindO I NV4 User s Manual ...
Page 1260: ...5 Editing User Accounts on the MICRO I 23 60 WindO I NV4 User s Manual ...
Page 1322: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual ...
Page 1414: ...4 E mail Function 28 66 WindO I NV4 User s Manual ...
Page 1554: ...3 Settings 34 14 WindO I NV4 User s Manual ...
Page 1642: ...2 Handling Problems 36 6 WindO I NV4 User s Manual ...
Page 1652: ...5 Text Alignment A 10 WindO I NV4 User s Manual ...
Page 1664: ...Index 12 WindO I NV4 User s Manual ...