1 Overview
30-10
WindO/I-NV4 User’s Manual
■
Output delay
The min-to-max delay time for the Output (#Q, #D and LEY) to fire from the expansion module is 1 millisecond to 1
milli the Execution Period.
■
Cyclic Script
A Cyclic Script refers to three processes: input refresh, I/O control (the specified script), and output refresh.
Refer to “4 Cyclic Script” on page 30-28 for programming information.
■
Sleep
Sleep refers to the time used by the Cyclic Script subtracted from the Execution Period. This is when the processor
executes display processing.
■
Execution Period
The Execution Period refers to one scan of the Cyclic Script (input r I/O c output refresh) and display
processing time (sleep).
The Cyclic Script is executed once every specified execution interval.
■
Display processing
Parts laid out on the screen are processed from top to bottom only when the Cyclic Script is in sleep mode.
Display processing pauses when execution of the next Cyclic Script begins, and resumes when the script goes to sleep
again.
When processing reaches the bottom of the screen, processing returns to the top of the screen.
When an output is sent to the expansion module immediately after the
output refresh ends, the output delay will be the longest because the
processor waits for the output refresh in the next scan before
reflecting the output to the Output (#Q, #D and LEY).
Output
External
output
Input refresh
Output refresh
I/O control
Sleep
(Display
processing
executed)
Input refresh
Output refresh
I/O control
Output delay
(maximum)
(#Q, #D, LEY)
• Only internal devices can be used in the Cyclic Script.
• The actual execution time of the Cyclic Script is stored in HMI Special Data Register LSD38 (current value
x ms), LSD39 (max value x ms), and LSD40 (min value x ms).
• Cannot use the LINE function, RECTANGLE function, CIRCLE function in the Cyclic Script.
• If execution of the Cyclic Script takes more than half of the time specified for the Execution Period, the
processor automatically extends the Execution Period so that the Cyclic Script completes within 1/2 of the
Execution Period. In this instance, error number 7 will be stored in HMI Special Data Register LSD53.
• If the execution time of the Cyclic Script exceeds 3,000 milliseconds, it pauses to allow the output refresh
to be executed. Thereafter, the script goes to sleep and the Cyclic Script executes on the next scan. In
this instance, error number 6 will be stored in HMI Special Data Register LSD53.
There is a delay in the I/O control. Take this delay time into consideration when specifying the Execution
Period. For instance, if it is necessary to capture external inputs within 100 ms, set the Execution Period to
80 ms.
Summary of Contents for MICRO/I HG4G-CJT22 F-B Series
Page 1: ...B 1701 11 User s Manual ...
Page 26: ...Preface 25 WindO I NV4 User s Manual ...
Page 106: ...5 WindO I NV4 Common Operations and Settings 2 74 WindO I NV4 User s Manual ...
Page 254: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual ...
Page 362: ...5 Screen Restrictions 5 28 WindO I NV4 User s Manual ...
Page 402: ...3 Text 7 30 WindO I NV4 User s Manual ...
Page 574: ...9 Potentiometer 8 172 WindO I NV4 User s Manual ...
Page 1052: ...4 Using the Data 15 22 WindO I NV4 User s Manual ...
Page 1170: ...6 Important Notes 20 60 WindO I NV4 User s Manual ...
Page 1200: ...5 Restrictions 22 18 WindO I NV4 User s Manual ...
Page 1260: ...5 Editing User Accounts on the MICRO I 23 60 WindO I NV4 User s Manual ...
Page 1322: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual ...
Page 1414: ...4 E mail Function 28 66 WindO I NV4 User s Manual ...
Page 1554: ...3 Settings 34 14 WindO I NV4 User s Manual ...
Page 1642: ...2 Handling Problems 36 6 WindO I NV4 User s Manual ...
Page 1652: ...5 Text Alignment A 10 WindO I NV4 User s Manual ...
Page 1664: ...Index 12 WindO I NV4 User s Manual ...