WindO/I-NV4 User’s Manual
3-79
5 User Communication
3
Communic
ation
Not set
Set
Set
Not set
Reception is started from the beginning and terminated with the terminal code.
Not set
Not set
Set
Reception is started from the beginning and the data is received according to the
maximum command length.
Reception is terminated when the Receiving Character Time Out occurs.
Not set
Reception is started from the beginning and terminated when the data is received
according to the length of the command.
Start code Terminal
code
Variable
Description of the procedure for terminal of data reception
<[LDR0100] N 2 2 U>
Receive data:
<<1:”AB” 2:”CD” [LDR0200]>>
Registering
Constant (Hexadecimal)
Device Address
'34' '35' '0d'
Constant
(Hexadecimal)
Receive
Command settings:
Start code: None
Terminal code 0dh
Skip(2)
<[LDR0100] N 2V 2 U>
Receive data:
Skip
“123”
Device Address With Variable
Maximum command length
Receive
Command settings:
Constant
(Character)
Start code: None
Terminal code: None
Skip(2)
<[LDR0100] N 2V 2 U>
Receive data:
Skip
“123”
Constant
(Character) Device Address With Variable
Receive
Command settings:
Start code: None
Terminal code: None
Receiving character time out occurs.
<[LDR0100] N 2 2 U>
Receive data:
<<1:”AB” 2:”CD” [LDR0200]>>
Registering Constant (Hexadecimal)
Device Address Without Variable
Command length
Receive
BCC(1 0 XOR N 1)
BCC
Command settings:
Start code: None
Terminal code: None
• When trigger conditions are satisfied for two or more receive commands for which both start code and
terminal code are set, all commands are analyzed and processed for receive processing. Since
commands with and without errors may be mixed depending on the results of data reception analysis of
each command, take extra caution regarding error handling.
• While the trigger condition is satisfied for a receive command for which either a start code or terminal
code is not set, only this command is processed for data reception when the trigger condition of another
command is being satisfied. When two or more commands exist for which either start code or terminal
code is not set, the command with the biggest number for managing the protocol is processed.
• When a start code of the receive command for which a start code is set cannot be received, all of the
receive data is ignored and abandoned. No error occurs.
• When start code is received with a receive command for which start code and terminal code are set, the
data reception is completed after the maximum number of bytes received in case of continuous
reception of data that does not match the terminal code of all receive command in which the trigger
conditions is satisfied.
Summary of Contents for MICRO/I HG4G-CJT22 F-B Series
Page 1: ...B 1701 11 User s Manual ...
Page 26: ...Preface 25 WindO I NV4 User s Manual ...
Page 106: ...5 WindO I NV4 Common Operations and Settings 2 74 WindO I NV4 User s Manual ...
Page 254: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual ...
Page 362: ...5 Screen Restrictions 5 28 WindO I NV4 User s Manual ...
Page 402: ...3 Text 7 30 WindO I NV4 User s Manual ...
Page 574: ...9 Potentiometer 8 172 WindO I NV4 User s Manual ...
Page 1052: ...4 Using the Data 15 22 WindO I NV4 User s Manual ...
Page 1170: ...6 Important Notes 20 60 WindO I NV4 User s Manual ...
Page 1200: ...5 Restrictions 22 18 WindO I NV4 User s Manual ...
Page 1260: ...5 Editing User Accounts on the MICRO I 23 60 WindO I NV4 User s Manual ...
Page 1322: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual ...
Page 1414: ...4 E mail Function 28 66 WindO I NV4 User s Manual ...
Page 1554: ...3 Settings 34 14 WindO I NV4 User s Manual ...
Page 1642: ...2 Handling Problems 36 6 WindO I NV4 User s Manual ...
Page 1652: ...5 Text Alignment A 10 WindO I NV4 User s Manual ...
Page 1664: ...Index 12 WindO I NV4 User s Manual ...