WindO/I-NV4 User’s Manual
3-137
7 BACnet Communication
3
Communic
ation
Analog Output Object
Present_Value of the Analog Output object can be allocated device addresses and set to the value of those device
addresses. Present_Value is a Float32(F) numeric value. When device addresses are allocated to Present_Value, the
product of Present_Value multiplied by 1/coefficient is stored in the device addresses.
The following diagram illustrates the concept when device addresses are allocated to Present_Value of the Analog
Output object and the BACnet device writes the analog output value.
When reading out Present_Value to device addresses, you must be aware of the data type. Depending on the data
type of the device addresses, the value is stored in the device addresses as follows. Set the data type according to the
value of Present_Value. The data type of Present_Value is set in “Conversion type” on page 3-115 of the “Analog
Output Object”.
BACnet objects
BACnet device
Device addresses
Physical output
Analog Output
object
Present_Value:
20.0
Priority_Array
#D0000: 1000
Coefficient: 0.02
External
analog output:
20 mA
Reflected
CH0: 20 mA
Write value:
20.0
Priority:
2
MICRO/I
Digital output module
Write from BACnet device
Read out to data register
Present_Value of the Analog Output object cannot be changed from the MICRO/I.
Data Type
Present_Value of BACnet Device
Value of Device Addresses
UBIN16(W)
Value within range of 0 to 65,535
Present_Value
Value outside range of 0 to 65,535
0
BIN16(I)
Value within range of -32,768 to 32,767
Present_Value
Value outside range of -32,768 to 32,767
0
UBIN32(D)
Value within range of 0 to 4,294,967,295
Present_Value
Value outside range of 0 to 4,294,967,295
0
BIN32(L)
Value within range of -2,147,483,648 to 2,147,483,647
Present_Value
Value outside range of -2,147,483,648 to 2,147,483,647
0
Float32(F)
—
Present_Value
Summary of Contents for MICRO/I HG4G-CJT22 F-B Series
Page 1: ...B 1701 11 User s Manual ...
Page 26: ...Preface 25 WindO I NV4 User s Manual ...
Page 106: ...5 WindO I NV4 Common Operations and Settings 2 74 WindO I NV4 User s Manual ...
Page 254: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual ...
Page 362: ...5 Screen Restrictions 5 28 WindO I NV4 User s Manual ...
Page 402: ...3 Text 7 30 WindO I NV4 User s Manual ...
Page 574: ...9 Potentiometer 8 172 WindO I NV4 User s Manual ...
Page 1052: ...4 Using the Data 15 22 WindO I NV4 User s Manual ...
Page 1170: ...6 Important Notes 20 60 WindO I NV4 User s Manual ...
Page 1200: ...5 Restrictions 22 18 WindO I NV4 User s Manual ...
Page 1260: ...5 Editing User Accounts on the MICRO I 23 60 WindO I NV4 User s Manual ...
Page 1322: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual ...
Page 1414: ...4 E mail Function 28 66 WindO I NV4 User s Manual ...
Page 1554: ...3 Settings 34 14 WindO I NV4 User s Manual ...
Page 1642: ...2 Handling Problems 36 6 WindO I NV4 User s Manual ...
Page 1652: ...5 Text Alignment A 10 WindO I NV4 User s Manual ...
Page 1664: ...Index 12 WindO I NV4 User s Manual ...