WindO/I-NV4 User’s Manual
33-7
2 Word Devices
33
In
terna
l Devices
■
HMI Special Data Register (LSD)
These registers (384
or 256
points) perform the following special operations.
*3 HG5G/4G/3G/2G-V only
*4 HG4G/3G, HG2G-5F/-5T, HG1G/1P only
*5 HG2G-5T, HG1G/1P only
Device Address
Function/Part
LSD0 to 3
Reserved
LSD4
Scan time Maximum value (msec.)
LSD5
Screen switch response time (msec.)
LSD6
Read scan communication time of External Device Communication 1 (msec.)
LSD7
Scan counter (incremented at each scan)
LSD8
1 second counter (incremented each second)
LSD9
10 msec. counter (increments every 10 msec.)
LSD10
100 msec. counter (incremented every 100 msec.)
LSD11
200 msec. counter (incremented every 200 msec.)
LSD12
500 msec. counter (incremented every 500 msec.)
LSD13
Stores the current Year data from the MICRO/I. “Year” (4 BCD digits)
LSD14
Stores current time data from MICRO/I. “Month” (2 BCD digits)
LSD15
Stores current time data from MICRO/I. “Day” (2 BCD digits)
LSD16
Stores current time data from MICRO/I. “Hour” (2 BCD digits)
LSD17
Stores current time data from MICRO/I. “Minute” (2 BCD digits)
LSD18
Stores current time data from MICRO/I. “Second” (2 BCD digits)
LSD19
Stores current time data from MICRO/I. “Day-of-week” (1 BCD digit)
0: Sunday
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
LSD20
When a value of “1” is written into this special register, the Internal clock in MICRO/I is updated
according to the data stored in LSD21-26. It automatically resets to “0” after the update.
LSD21
Write a “Year” value to store in the MICRO/I internal clock. (2 BCD digits)
LSD22
Stores set value for “Month” in MICRO/I internal clock. (2 BCD digits)
LSD23
Stores set value for “Day” in MICRO/I internal clock. (2 BCD digits)
LSD24
Stores set value for “Hour” in MICRO/I internal clock. (2 BCD digits)
LSD25
Stores set value for “Minute” in MICRO/I internal clock. (2 BCD digits)
LSD26
Stores set value for “Second” in MICRO/I internal clock. (2 BCD digits)
LSD27
Scan time Current value (msec.)
LSD28
Scan time Minimum value (msec.)
LSD29, 30
Reserved
LSD31
Stores the currently displayed screen number.
LSD32
Set a value ( in reference to a Base Screen number you want to switch to) and it will automatically
switch to a specified Base Screen number.
Note, after switching to a Base Screen, the value stored automatically resets to 0.
LSD33
USB flash drive error status
0: Normal
1: A write occurred when the USB flash drive was not inserted or when an incompatible USB flash
drive was inserted
2: Format error
3: Access error, Insufficient memory in USB flash drive or Reading or writing failure
4: Unsuccessful read of picture data
Summary of Contents for MICRO/I HG4G-CJT22 F-B Series
Page 1: ...B 1701 11 User s Manual ...
Page 26: ...Preface 25 WindO I NV4 User s Manual ...
Page 106: ...5 WindO I NV4 Common Operations and Settings 2 74 WindO I NV4 User s Manual ...
Page 254: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual ...
Page 362: ...5 Screen Restrictions 5 28 WindO I NV4 User s Manual ...
Page 402: ...3 Text 7 30 WindO I NV4 User s Manual ...
Page 574: ...9 Potentiometer 8 172 WindO I NV4 User s Manual ...
Page 1052: ...4 Using the Data 15 22 WindO I NV4 User s Manual ...
Page 1170: ...6 Important Notes 20 60 WindO I NV4 User s Manual ...
Page 1200: ...5 Restrictions 22 18 WindO I NV4 User s Manual ...
Page 1260: ...5 Editing User Accounts on the MICRO I 23 60 WindO I NV4 User s Manual ...
Page 1322: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual ...
Page 1414: ...4 E mail Function 28 66 WindO I NV4 User s Manual ...
Page 1554: ...3 Settings 34 14 WindO I NV4 User s Manual ...
Page 1642: ...2 Handling Problems 36 6 WindO I NV4 User s Manual ...
Page 1652: ...5 Text Alignment A 10 WindO I NV4 User s Manual ...
Page 1664: ...Index 12 WindO I NV4 User s Manual ...