Alar
m ID
Alarm
Name
Alar
m
Sever
ity
Occurren
ce
Condition
s
Possible Causes
Solutions
a013 Comp
dischar
ge HT
lock
Critic
al
A
compresso
r has
generated
six high
discharge
temperatu
re alarms
within
one
consecutiv
e hour or
a
compresso
r high
discharge
temperatu
re alarm
has not
cleared
within 20
minutes.
The a012 comp
discharge HT alarm is
generated frequently.
Reference to the
solutions for the
a012 comp
discharge HT
alarm.
a014 Comp
short
period
Warni
ng
A
compresso
r has been
switched
off and on
10 times
during the
monitored
period,
and each
running
period is
less than
1.5 times
of the
shortest
configure
d running
period.
1. The comp starts
and stops
frequently, affected
by other alarms.
2. The load is low,
which leads to the
comp starting and
stopping
frequently.
1. Clear other
alarms.
2. Please consult
Huawei
technical
support.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
7 System Operation and Maintenance
Issue 12 (2020-10-28)
Copyright © Huawei Technologies Co., Ltd.
164