Figure 7-21 Removing butterfly buts and water pan
Step 5 Remove the screws that secure the sheet metal, as shown by 2 in
NO TICE
● Remove the infrared humidifier lamp. For details, see
NetCol8000–A050 device as an example.
● There are two humidifier cable fasteners in the NetCol8000–A100: one on the
right and the other on the left. You need to remove both of them.
Step 6 Loosen the bolts of the damaged lamp tube from the ceramic terminal block while
holding the ends of the lamp tube with hands.
Step 7 Take out the lamp tube and install a new lamp tube.
Step 8 Reassemble the infrared humidifier in an inverse order of
.
Step 9 Power on the unit and tap Maint > Diagnostic Mode > Enter, open the solenoid
valve and the humidifier. Make sure they work properly. Exit the Diagnostic Mode.
Step 10 Tap Maint > Performance Maint to clear the humidifier total runtime.
----End
Replacing a Water Supply Valve
Recommended tools and materials for replacing a water supply valve: a Phillips
screwdriver, an adjustable wrench, and a new water supply valve
Step 1 Disconnect the main power supply. Stop the water supply to the infrared
humidifier.
Step 2 Pull out the wiring terminals on the solenoid valve control cable using
combination pliers, and remove the screws that secure the water injection solenoid
valve to the baffle plate.