Alar
m ID
Alarm
Name
Alar
m
Sever
ity
Occurren
ce
Condition
s
Possible Causes
Solutions
a011 Comp
LP lock
Critic
al
A
compresso
r has
triggered
six low
pressure
protection
s within
one
consecutiv
e hour, or
a
compresso
r low
pressure
alarm has
not
cleared
within 30
minutes.
The a010 comp LP
alarm is generated
frequently.
Reference to the
solutions for the
a010 comp LP
alarm.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
7 System Operation and Maintenance
Issue 12 (2020-10-28)
Copyright © Huawei Technologies Co., Ltd.