(10) Outdoor unit
(11) Inverted trap
(12) Dry filter
(13) Liquid pipe needle valve
(14) Solenoid valve
(15) Sight glass
(16) Thermostatic expansion
valve
(17) Needle valve after the
thermostatic expansion valve
(18) Distributor
(19) Evaporator coil
(20) Indoor fan
(21) Freeze point protecting
switch
(22) Low pressure switch
(23) Sensing bulb
(24) Low pressure needle valve
(25) Suction pipe
NO TE
● The pipes in real line are installed by Huawei before delivery.
● The pipes in dash are to be routed onsite by technical personnel.
● Huawei does not provide the inverted trap (component 11) and oil traps (component 9)
used in the scenario where the outdoor unit is placed higher than the indoor unit.
However, to ensure the normal operating and easy maintenance of the NetCol8000-A, it
is recommended that you use these two components.
Installation Layout Principles
Layout principles for installing the NetCol8000-A:
If the outdoor unit is placed higher than the indoor unit, install an oil trap every 5
m to 6 m along pipes in the vertical direction.
show the
parameters of oil trap and inverted traps.
●
If the outdoor unit is placed higher than the indoor unit:
NO TICE
The inverted trap should be higher than the top copper pipe of the condenser in
the outdoor unit.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
3 Installation Guide
Issue 12 (2020-10-28)
Copyright © Huawei Technologies Co., Ltd.
37