Alar
m ID
Alarm
Name
Alar
m
Sever
ity
Occurren
ce
Condition
s
Possible Causes
Solutions
a084 Power
fault
Critic
al
N/A
1. No voltage jumper
is connected to the
smart cooling
product unit.
2. The voltage jumper
is faulty.
1. Connect a
correct
voltage
jumper to the
smart cooling
product unit.
2. Maintain or
replace the
voltage
jumper.
a085 Route
A fuse
discon
nect
Critic
al
The
compresso
r control
loop fuse
reports
that the
switch
polarity is
different
from the
preset
polarity
when the
alarm
detection
delay
expires.
1. A device on loop A
is faulty.
2. The loop A fuse is
loose, aged, or
disconnected.
1. Maintain or
replace the
faulty device
on loop A.
2. Maintain or
replace the
fuse.
a086 Route
B fuse
discon
nect
Critic
al
The
compresso
r control
loop fuse
reports
that the
switch
polarity is
different
from the
preset
polarity
when the
alarm
detection
delay
expires.
1. A device on loop B
is faulty.
2. The loop B fuse is
loose, aged, or
disconnected.
1. Maintain or
replace the
faulty device
on loop B.
2. Maintain or
replace the
fuse.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
7 System Operation and Maintenance
Issue 12 (2020-10-28)
Copyright © Huawei Technologies Co., Ltd.
176