No.
Parameters
Note
3
Active/Standby
Active: properly responds to the requirement
control.
Standby: responds to the requirement control
when Active is faulty (critical alarms,
shutdown, and offline) or Active cannot meet
cooling requirements.
4
Frame: green/non-
green
A device with green frame indicates the
device itself, as shown in
.
A non-green frame indicates the other device
in the group, as shown in
.
5
Ground color: red,
bright gray
Red indicates that a critical alarm is
generated, as shown in
.
Bright gray indicates that the device is
operating without any critical alarms, as
shown in
.
----End
Follow-up Procedure
After you have completed the settings, perform the following checks to confirm
whether the teamwork control is available:
1. Check whether the device number on the topology is the same as the actual
device number.
–
If yes, go to
.
–
If no, check the cable connection and the settings of teamwork control
parameters.
2. Check whether the number of the active devices on the topology is the same
as the actual device number.
–
If yes, go to
.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
5 ACC Introduction
Issue 12 (2020-10-28)
Copyright © Huawei Technologies Co., Ltd.
111