No.
Name
Configurati
on
Outer
Diameter
and
Thickness
(mm)
Technical
Requirements
Remarks
2
7/8 inch
inverted
trap of
gas
pipes
Optional
Φ22.2 x
1.02
The flaring inner
diameters at both
ends of the
copper pipe are
22.6 mm.
3
5/8 inch
inverted
trap of
liquid
pipes
Optional
Φ15.88 x
1.0
The flaring inner
diameters at both
ends of the
copper pipe are
16.3 mm.
4
1 inch
oil trap
Optional
Φ25.4 x 1.2
The flaring inner
diameter of
copper pipe is
25.8 mm, and
shrinking
diameter is 22.6
mm.
5
1 inch
inverted
trap of
gas
pipes
Optional
Φ25.4 x 1.2
The flaring inner
diameter of
copper pipe is
25.8 mm.
6
3/4 inch
inverted
trap of
liquid
pipes
Optional
Φ19.05 x
1.0
The flaring inner
diameter of
copper pipe is
19.4 mm.
Humidifier Water Supply Pipe and Drainpipe
Two humidifier water supply pipe modes are provided:
●
Rigid pipe: Prepare rigid pipes and connectors same as parts 2 and 3 in A of
.
●
Hose: Prepare hoses and pagoda connectors same as parts 4 and 6 in B of
.
NO TICE
The sum of calcium and magnesium cannot exceed 600 mg/L.
Drainpipes must be able to withstand temperatures higher than 85°C. Otherwise,
the pipes may be deformed.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
3 Installation Guide
Issue 12 (2020-10-28)
Copyright © Huawei Technologies Co., Ltd.
32