![Huawei NetCol8000-A Series User Manual Download Page 175](http://html.mh-extra.com/html/huawei/netcol8000-a-series/netcol8000-a-series_user-manual_166611175.webp)
Alar
m ID
Alarm
Name
Alar
m
Sever
ity
Occurren
ce
Condition
s
Possible Causes
Solutions
a019 Humid
ifier
pan
water
level
high
Critic
al
The high
water
level
detection
switch for
the
infrared
humidifier
water pan
is
disconnect
ed when
the alarm
detection
delay
expires.
1. The pan's drainpipe
is blocked or
located higher
than the water
level in the pan.
2. The overflow
outlet on the
humidifier is dirty
or blocked.
3. Cables to the high
water level
detection switch
are loose or
damaged.
4. The high water
level detection
switch is faulty.
1. Maintain or
replace the
drainpipe.
2. Maintain or
replace the
humidifier.
3. Check cables
to the high
water level
detection
switch.
4. Maintain or
replace the
high water
level
detection
switch.
a020 Humid
ifier
pan no
water
Major The dry
heating
protection
temperatu
re switch
for the
infrared
humidifier
water pan
is
triggered,
and the
filter
clogging
switch is
closed
and does
not
recover
for N s.
1. The humidifier
water pan has
insufficient water.
2. The manual reset
temperature switch
has not been reset.
3. Cables to the
humidifier
temperature
switches are loose
or damaged.
4. Temperature
switches are faulty.
1. Solve the
water
insufficiency
problem.
2. Reset the
manual reset
temperature
switch.
3. Check cables
to the
humidifier
temperature
switches.
4. Maintain or
replace the
humidifier
temperature
switches.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
7 System Operation and Maintenance
Issue 12 (2020-10-28)
Copyright © Huawei Technologies Co., Ltd.
166