Figure 5-18 Exporting an MIB file successfully
5.4.7 Setting Teamwork Control Parameters
Prerequisites
Assign teamwork group number and teamwork unit address for the teamwork
controlled smart cooling products as follows:
●
Teamwork group no.: Group the smart cooling products in adjacent areas as
one, that is, assign one teamwork control number for them. At most four
teamwork control groups can be assigned (1–4).
●
Teamwork unit address: The address for the smart cooling product in the
same group cannot be the same (address range: 1–32). The smart cooling
product addressed 1 is the master one that collects, processes, and delivers
data. Set the unit address numbers from one to the Total number of units in
this group.
Context
●
The parameters in this section are for reference only. Set actually parameter
values as required.
●
To change teamwork settings, log in as the Admin or Engineer user.
Procedure
Step 1 On the home screen, tap
> Teamwork Settings.
Step 2 Set teamwork control parameters.
You can set all the teamwork control parameters on the master smart cooling
product but only Teamwork group no., Teamwork unit address, and Teamwork
function on a slave smart cooling product, other parameters of the slave smart
cooling products will be modified by the master smart cooling product
synchronously.
describes how to set the parameters.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual