Alar
m ID
Alarm
Name
Alar
m
Sever
ity
Occurren
ce
Condition
s
Possible Causes
Solutions
a010 Comp
LP
Major The
compresso
r low
pressure
switch is
disconnect
ed when
the alarm
detection
delay
expires.
1. The refrigerant
leaks.
2. The solenoid valve
is faulty.
3. Cables to the low
pressure switch are
loose or damaged.
4. The low pressure
switch is faulty.
5. The dryer filter is
blocked.
6. The expansion
valve is blocked.
7. The indoor fans are
faulty.
1. Check for any
leakages. Fill
refrigerant
after
maintenance
or
replacement.
2. Maintain or
replace the
solenoid coil
or solenoid
valve.
3. Check cables
to the low
pressure
switch.
4. Maintain or
replace the
low pressure
switch.
5. Maintain or
replace the
dryer filter.
6. Maintain or
replace the
expansion
valve.
7. Maintain or
replace the
indoor fans.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
7 System Operation and Maintenance
Issue 12 (2020-10-28)
Copyright © Huawei Technologies Co., Ltd.
161