Alar
m ID
Alarm
Name
Alar
m
Sever
ity
Occurren
ce
Condition
s
Possible Causes
Solutions
a012 Comp
dischar
ge HT
Major The
compresso
r
discharge
temperatu
re switch
is
disconnect
ed when
the alarm
detection
delay
expires.
1. The refrigerant
leaks.
2. Cables to the
discharge
temperature switch
are loose or
damaged.
3. The ambient temp
is high.
4. The discharge
temperature switch
is faulty.
5. Outdoor fans are
faulty.
6. The condenser fins
are blocked.
1. Check for any
leakages. Fill
refrigerant
after
maintenance
or
replacement.
2. Clean the
condenser
fins.
3. Check the
ambient
temperature.
4. Check cables
to the
discharge
temperature
switch.
5. Maintain or
replace the
discharge
temperature
switch.
6. Maintain or
replace the
outdoor units.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
7 System Operation and Maintenance
Issue 12 (2020-10-28)
Copyright © Huawei Technologies Co., Ltd.
163