Symptom
Possible Cause
Reference Solution
The low pressure switch
reacts.
Check the low pressure
switch status.
The exhaust temperature
switch reacts.
Check the exhaust
temperature switch status.
Circuit breakers, fuses, or
cables are disconnected.
Check the main circuit
breaker, compressor circuit
breakers, fuses, and cables.
An indoor fan does not
work at a high speed.
Check whether the indoor
fan works at a high speed.
A compressor motor is
damaged.
Replace the compressor.
A compressor does not
need to start.
Check for any startup
requirement on the LCD.
The compressor
exhaust
temperature is too
high.
The outdoor unit is not
properly installed. The
outdoor units must not be
exposed to direct sunshine,
and must be installed at
distances required by the
installation manual.
Properly install the outdoor
units. Do not expose them
to direct sunshine, and
verify that the distances
meet requirements in the
installation manual.
Check whether the air
exhaust pressure is too
high.
If the air exhaust pressure
is too high, re-inject
refrigerant to expel free air
from the cooling loop.
Heat dissipation is poor
because the condenser is
dirty or blocked.
Clean the condenser fins.
The outdoor fan fails.
Check whether the outdoor
fan works properly.
Check whether the
refrigerant amount is
properly (the low pressure
is too low).
Verify that the amount of
refrigerant is proper.
The compressor
exhaust
temperature is too
low.
Refrigerant is leaking.
Check the pipeline for any
leakage.
The compressor
suction pressure is
too low or liquid
returns.
Refrigerant is insufficient.
Add more refrigerant.
The indoor temperature is
set too low.
Increase the temperature
setting.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
7 System Operation and Maintenance
Issue 12 (2020-10-28)
Copyright © Huawei Technologies Co., Ltd.
180