Alar
m ID
Alarm
Name
Alar
m
Sever
ity
Occurren
ce
Condition
s
Possible Causes
Solutions
a026 Air
filter
exceed
runtim
e
Warni
ng
The
cumulativ
e running
period of
air filters
(counting
from the
time
when the
NetCol800
0-A starts
or the
fans begin
to work)
is greater
than or
equal to
the alarm
threshold.
The accumulated
runtime of the air
filters exceeds the
alarm threshold.
Maintain or
replace the air
filter and clear
the accumulated
runtime.
a027 Power
loss
Warni
ng
The
power
supply is
lost
during
normal
operation.
When a
restart is
initiated,
the main
control
board
checks the
NetCol800
0-A state.
If a cold
reset is
required,
this alarm
is
generated.
If a hot
reset is
required,
this alarm
is not
generated.
The supply power is
cut off.
Check the power
supply cables.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
7 System Operation and Maintenance
Issue 12 (2020-10-28)
Copyright © Huawei Technologies Co., Ltd.
169