Paramete
r
Description
Configuration
Principle
Default Value
Cascade
After the
requirement control
is enabled, you can
configure Cascade.
The cascade function
starts standby smart
cooling products if
the active one
cannot meet the
refrigerating
requirements.
If the heat load to
the device increases,
the cascade function
is recommended.
Disable
Step 3 Complete the teamwork settings for all the smart cooling products by performing
Step 4 On the home screen of any teamwork controlled smart cooling product, tap
. If the teamwork control succeeds, the teamwork topology of the smart
cooling product in the group is displayed, as shown in
.
describes the note for the screen.
Figure 5-19 Teamwork topology
Table 5-7 Note for the screen
No.
Parameters
Note
1
ON/OFF/NA
On indicates the smart cooling product is
started and Off indicates the smart cooling
product is shut down. NA indicates the smart
cooling product is offline.
2
01, 02, 03
Indicates the device address. 01 is the master
one and the rest are all slave ones.
NOTE
If the master one offline, the teamwork networking
failed.